33
0100037-J0 Rev C
11. Troubleshooting
The rectifiers and the shelves are designed for simple installation and reliable, trouble-free operation for several
years.
In most cases the rectifiers will recover from minor alarms and faults automatically. However under certain conditions
the rectifiers may need remote control. And under very rare cases the rectifier may need a manual reset (unplug and
reinsert the rectifier). In the unlikely event of a rectifier failure, it may need replacement.
A 3.0KW rectifier shelf can have 4 or 5 rectifiers in it, depending on the model. The rectifiers have 3 LED indicators
that provide information about the system. Refer to the LED section, 4.1.1 on page 11 for details.
When the 3.0KW shelf system is used in conjunction with a controller, detailed system informations and status can
be obtained through it. Even more information can be obtained using the web interface using the Ethernet port.
Table below provides a quick look up at the LEDs and the corresponding rectifier states.
Table I —
3.0 kW Rectifier - Alarm and Fault States
AC
DC
Alarm/Fault
Rectifier State
Possible
Causes
Solutions
Green
Green
Off
Normal operation
Green
Off
Off
Unit has no DC output
Unit is in Power
Save mode
Unit will automatically
resume power delivery
power when load is
increased or when the
Remote restart is enabled.
Off
Off
Off
Unit may not be plugged in or
system is off or unit has failed
Plug in unit completely,
check AC and DC wiring
Off
Off
Red
Unit has shut down due to
a fault and may need to be
reset. Check controller or web
interface to find the fault details
AC not qualified unit
has failed
Green
Off
Red
Unit has shut down due to
a fault and may need to be
reset. Check controller or web
interface to find the fault details
Depending on the
fault the unit may
or may not recover
automatically
Over temperature fault, will
auto recover, plug unit into
the shelf
Green
Off
Blinking Red
Unit has an alarm
Check the controller front
panel or web interface to
find out the details of the
alarm
Green
Green
Blinking Red
Unit has an alarm.
Check the controller front
panel or web interface to
find out the details of the
alarm
Green
Green
Red
Normal Operation
Unit is on No LOAD,
and no battery is
connected. CXC will
report ramp test fail.
Add load or connect
battery, or disable ramp
test