23
0100037-J0 Rev C
7.6 DC Output Connections - Bulk Distribution
WARNING!
Do not complete the final live connections to the battery. Leave open and insulate the
final connections or remove the battery fuses. Switch off the battery contacts if used.
The DC output wires must be UL approved XHHW or RHH/RHW (RW90 type for Canadian users). Control and
sense wires must be UL approved Style 1015 (TEW type for Canadian users).
The common output leg of the rectifier system must be connected to the ground. This is typically done at the load
common termination point.
The 23" and 19" bulk distribution models have positive and negative output bars.
Figure 10 — Positive and Negative Output Bars on 23" and 19" Bulk Distribution Models
POSITIVE (+)
OUTPUT BAR
NEGATIVE (-)
OUTPUT BAR