0100037-J0 Rev C
24
7.6.1 Busbar Connection
Multiple shelves can be connected directly to customers’ vertical busbar.
1. Remove the bolts and washers at both positive and negative output bars. Bolts are 3/8-16 x 1", and can accom-
modate up to 1/4" thick busbar.
2. Use fasteners removed from the previous step to secure the vertical busbars to shelf positive and negative out-
put bars. Install all fasteners “FINGER TIGHT”, then apply 20 ft-lbf torque to each bolt.
3. Refer to the system startup procedure before connecting batteries online.
7.6.2 Cable Connection
When attaching cables directly to the output bars, use appropriately sized cables terminated with crimp lugs with
3/8" holes on 1" centers.
1. Remove the bolts and washers at both positive and negative output bars. Bolts are 3/8-16 x 1"
2. Use fasteners removed from the previous step to secure the positive and negative cables to the shelf output
bars. Install all fasteners “FINGER TIGHT”.
3. Use a “Tongue and Groove” or similar pliers to hold and stabilize the output bar, torque each bolt to 20 ft-lbf.
CUSTOMERS' VERTICAL
BUS BAR, NEGATIVE (-)
CUSTOMERS' VERTICAL
BUS BAR, POSITIVE (+)
INSTALL ALL FASTENERS "FINGER TIGHT",
THEN APPLY 20 ft-lbf TORQUE TO EACH BOLT
Figure 11 — Connecting Output Bars to Customer's Vertical Busbars
Figure 12 — Connecting Output Bars Directly to Cables
TONGUE AND GROOVE
PLIER TO STABILIZE
THE BAR WHEN
TORQING WIRE LUG
TORQUE TO 20 ft-lbf