ENERGY WALL
TM
U-ERV/U-HRV
Discrete Inputs
Discrete Inputs are boolean (on/off) values that are read only
Name
Modbus
Address
BACnet
ID
Description
Unit Enable
10001
95
This indicates the unit is enabled.
ID1 (J8-1)
10002
104
This will read on when the output is floating, zero when grounded.
ID2 (J8-2)
10003
105
NO1 (J10-1)
10004
106
Normally open relays; on indicates the relay has been closed.
NO2 (J10-3)
10005
107
NO3 (J11-1)
10006
108
NO4 (J11-3)
10007
109
NO5 (J11-5)
10008
110
Relay 6 (J12-1 and -2)
10009
111
On indicates this relay is closed.
Input Registers (read only values)
Name
Modbus
Address
BACnet
ID
Format
Description
Fan
Tachometers
30001 - 30040
17 - 56
16 bit
signed
integer
Indicates the RPM of each possible fan. If a fan is not
present or operating, RPM will be -1 (See Fan Section)
Fault Status
30041
85
16 bit
integer
This is a bit field indicating any faults that are present.
(See section below)
Supply Air
Temperature
30042 - 30043
86
32 bit
floating
point.
The temperature in degrees C. If no sensor installed, the
value will be 2000
Outside Air
Temperature
30044 - 30045
87
Exhaust Air
Temperature
30046 - 30047
88
Return
Air
Temperature
30048 - 30049
89
OPERATION
BACNET/MODBUS POINTS