5
ESC Series
Boiler Model
Input (MBH)
Output (MBH)
Net I=B=R
Water (MBH)
AFUE (%)
ESC3
70
60
52
85.5
ESC4
105
90
78
85.4
ESC5
140
120
104
85.3
ESC6
175
150
130
85.2
ESC7
210
179
156
85.0
ESC8
245
208
181
84.5*
ESC9
280
238
207
84.0*
* Do not meet ENERGY STAR requirements
Ratings
SPECIFICATIONS
Boiler
Model Depth Width Height
Supply NPT
(inch)
Return
NPT (inch)
Vent
(inch)
Air
Intake
(inch)
Gas NPT
(inch)
Relief Valve
NPT
(inch)
Drain
IPS
(inch)
ESC3
33
12¾
41
1¼
1¼
3
3
½
¾
¾
ESC4
33
15½
41
1¼
1¼
3
3
½
¾
¾
ESC5
33
18½
41
1¼
1¼
3
4
½
¾
¾
ESC6
33
21½
41
1¼
1¼
3
4
½
¾
¾
ESC7
33
24¾
41
1¼
1¼
3
5
¾
¾
¾
ESC8
33
27¾
41
1¼
1¼
4
5
¾
¾
¾
ESC9
33
30¾
41
1¼
1¼
4
5
¾
¾
¾
Dimensions, Weights and Connections
Electrical Requirements: 120VAC, 60 Hz, 1-ph, 15A
Boiler
Model
Allowable Supply Water
Temperature (°F)
Minimum Return Water
Temperature (°F)
Minimum Flow
(GPM)
Waterside Pressure Drop
at 20°F
D
T (Ft. of Head)
ESC3
130-220
110
None
<1
ESC4
130-220
110
None
<1
ESC5
130-220
110
None
<1
ESC6
130-220
110
None
<1
ESC7
130-220
110
None
<1
ESC8
130-220
110
None
<1
ESC9
130-220
110
None
<1
Water Temperatures and Flows
Boiler Model
Shipping Weight (lbs)
Empty Weight (lbs)
Water Content (gal)
ESC3
250
170
2
ESC4
300
220
3
ESC5
350
270
4
ESC6
410
320
5
ESC7
460
370
5
ESC8
510
420
6
ESC9
560
470
7
Weights and Volume
Summary of Contents for ESC
Page 6: ... Figure S 1 Minimum Clearances to Combustibles SPECIFICATIONS continued ...
Page 30: ...30 Internal Wiring Figure IW 1 Wiring Diagram ...
Page 31: ...31 Internal Wiring continued Figure IW 2 Wiring Diagram ...
Page 37: ...37 APPENDIX B1 INTENTIONALLY OMITTED ...
Page 50: ...50 Figure D 0 Piping Schematic Symbols APPENDIX D System Piping continued ...
Page 62: ...62 SERVICE RECORD DATE SERVICE PERFORMED ...