EK-Pak Owner and Installation Manual
EK-Pak Owner & Installation Manual First Edition December 2002
19
Flush, Purge, and Fill System with Water:
Follow these steps to flush, purge, and fill the system. Do not allow system pressure to exceed 30 psi.
♦
Flush
dirt, debris, and solder flux from system through the
strainer drain
.
o
Turn off power to the system.
o
Close purge ball valve.
o
Connect hose to
strainer drain
and open fully.
o
Manually open one zone valve.
o
Open heating module water feed. Water will begin to flow through open zone.
o
Open the next zone manually before closing the flushed zone valve.
o
Repeat until all zones have been flushed and then close the
strainer drain
.
♦
Purge
air from system through the
purge drain
.
o
Move drain hose to
purge drain
from the strainer drain.
o
Open purge drain and verify purge ball valve is closed.
o
Manually open one zone valve.
o
Open heating module water feed. Water will begin to flow through open zone.
o
Open the next zone manually before closing the purged zone valve.
o
Repeat until all zones have been purged.
o
Close
the
purge drain
and open the purge ball valve.
♦
Fill
the system through the heating module feed.
o
Adjust to normal cold system pressure, 10 to 12 psi on pressure gauge.
o
Add pressure if too low, relieve pressure if too high.
Once the system has been properly flushed and purged, the system will vent any released air
during operation.
NOTICE: AIR VENT CAP MUST REMAIN OPEN.
Vent cap should be removed and
kept in a safe location.
NOTICE:
DO NOT START BURNER UNTIL THE SYSTEM IS FULL OF
WATER.
Before placing system in operation, carefully check for leaks throughout system. Tighten
pipe joints, circulator flanges; check gaskets, etc., as needed.
Heating module Water Treatment:
Addition of heating module water treatment is recommended to reduce lime buildup inside
the heating module. Energy Kinetics recommends addition of one quart of 8-Way Boiler
Treatment per 30 gallons system water. 8-Way Boiler Treatment is recommended to treat
water up to medium hardness. Call Energy Kinetics for more details about heating module
water treatment and about hard water conditions.
Anti-Freeze:
Only non-toxic antifreeze (such as Propylene Glycol) should be used if adding anti-freeze
to a system that produces domestic hot water. Hard water should not be used in combination
with generic antifreeze. Energy Kinetics supplies a quality inhibited Propylene Glycol anti-
freeze with orange dye and an antifoam agent. 8-Way Boiler Treatment can be added to
Energy Kinetics anti-freeze and is recommended in areas of medium water hardness.
NOTICE:
Thoroughly clean system prior to adding antifreeze.
TSP is recommended for
removing flux and other oil based compounds. Once system has been cleaned and flushed,
then add antifreeze to obtain approximately a 30% by volume mixture of antifreeze in water.
Call Energy Kinetics for assistance in calculating how much anti-freeze to add to system.
Winterizing
The EK-Pak heating module comes equipped with heaters to discourage the unit from
freezing. For these heaters to work, there must be electrical power to the unit. This freeze
prevention system will not work if the electrical power source has been disconnected.