Operating Manual
Arc fa
ult protection ZŁ-4A; (07.2019)
83
The device includes the Modbus RTU Slave protocol. There are the primary inquiries sup-
ported, namely #03
– Read Holding Registers, #06 – Preset Single Register, #16 – Preset
Multiple Registers. In case of receiving a Modbus frame, which includes some errors, the
device displays the error code according to the table below.
Error code
Meaning
Description
1
Illegal Function
Function is not supported
2
Illegal Data Address
Unacceptable register (or registers) address (or addresses)
3
Illegal Data Value
Unacceptable range of information (i.e. the amount of registers)
4
Slave Device Failure
Register record error
– the value of register is beyond the acceptable range
Available registers.
M1 Block of registers
There are the following 16-bit registers with the attribute read only [R] (base address: 4000)
available:
offset
Register name
Description
0
DeviceSignature
Device identification, the signature has a constant value:
0xaa
1
DeviceCode
Device identification code, constant value:
0x01
(the central unit)
2
DeviceSerialNumber L
Factory device number (the serial number)
– lower byte
3
DeviceSerialNumber H
Factory device number (the serial number)
– higher byte
4
FirmwareVersion
Firmware Version; 0x12 means v1.2
5
DeviceAlarms
Device Alarms
6
DeviceEvents
Events Register
7
RelayState
Register including the executive relays status
8
RelayMode.RelayP1
Relay P1 working status
9
RelayMode.RelayP2
Relay P2 working status
10
RelayMode.RelayP3
Relay P3 working status
11
RelayMode.RelayP4
Relay P4 working status
12
RelayMode.RelayP5
Relay P5 working status
13
RelayMode.RelayP6
Relay P6 working status
14
RelayMode.DiodeL1
Signal diode L1 working mode
15
UnitsStatus.RegisteredUnits
Register including the total amount of all installed JP/JW units
16
UnitsStatus.PresentUnits
Register including the amount of the installed JP/JW units present in the net-
work
17
UnitsStatus.AbsentUnits
Register including the amount of the installed JP/JW units not present in the
network
18
UnitsStatus.AddressCollision
Register including the amount of the installed JP/JW units with wrong network
addresses
19
UnitsStatus.SensorFailure
Register including the amount of the installed bay units with damaged optical
sensors (permanent damaged)
20
UnitsStatus.SensorSet
Register including the amount of the installed bay units with activated optical
sensors
21
UnitsStatus.RelaySetUnits
Register including the amount of the installed bay units with activated relay
inputs
22
UnitsStatus.ZoneS1Mode
Register
including the amount of the installed bay units with activated “tripping
mode in zone S1”
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...