Operating Manual
30
Arc fault
protection ZŁ-4A; (07.2019)
Fig. 11
ZŁ-4A elements connection (with terminal).
Cable diameter should be adjusted to the length of the cable which connects the ele-
ments of the arc protection (see Table 1). For the cable length lesser than 100 m the diame-
ter of a single conductor should be not less than 0.5 mm2 (screened cable type LIYCY-P
2x2x0.5 mm2 is recommended). While for the cable length greater than 100 m the conductor
diameter should be not less than 1 mm2 LIYCY-P 2x2x1 mm2 recommended.
Connection of units to CAN bus:
•
CAN L clamps (A9 for JP/JW, B1 for JC) with CAN L line
•
CAN H clamps (A8 for JP/JW, B2 for JC) with CAN H line
In case of the last unit in a chain the terminator should be activated by closing contacts CAN
RL, CAN RH, CAN R (A5, A6, A7 for JP, B3, B4, B5 for JC). Connections diagram of several
ZŁ-4A devices is presented in figures Fig. 14, Fig. 15 and Fig. 16. The cable screen should
be connected to the PE clamp in the place of the JC installation. In other places the screen
should be terminated as close as possible to the JP/JW and then insulated.
Table 1 Conductors ensuring secure connections
Conductor cross
section
Rated data
CAN BUS and 24V DC power supply (<100 m)
2x2x0.5 mm
2
LIYCY-P, 250V rms; or
dedicated cable to CAN BUS
CAN BUS and 24V DC power supply (>100 m)
2x2x1 mm
2
RS485
0,35-0,75 mm
2
Dedicated cable to RS485
External conductor connections
1.5 mm
2
250V rms;
Grounding
≥ 2.5 mm
2
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...