Operating Manual
84
Arc fault
protection ZŁ-4A; (07.2019)
23
UnitsStatus.ZoneS2Mode
Register including the amount of the installed bay units with activated “tripping
mode in zone S2”
24
UnitsStatus.ZoneS3Mode
Register including the amount of the installed bay units with activated “tripping
mode in zone S3”
25
UnitsStatus.ZoneS1Set
Register including the amount of the bay units that have tripped in zone 1
(event is recorded in the central unit)
26
UnitsStatus.ZoneS2Set
Register including the amount of the bay units that have tripped in zone 2
(event is recorded in the central unit)
27
UnitsStatus.ZoneS3Set
Register including the amount of the bay units that have tripped in zone 3
(event is recorded in the central unit)
28
UnitsStatus.StatusZoneS1Set
Register including the amount of the bay units that have tripped in zone 1 (sta-
tus is read on the fly
29
UnitsStatus.StatusZoneS2Set
Register including the amount of the bay units that have tripped in zone 2 (sta-
tus is read on the fly)
30
UnitsStatus.StatusZoneS3Set
Register including the amount of the bay units that have tripped in zone 3 (sta-
tus is read on the fly)
31
UnitsStatus.FlashTestOkUnits
Number of bay units which passed the optical sensors test
32
UnitsStatus.FlashTestFailUnits
Number of bay units which have not passed the optical sensors test
33
RemoteRelayMode.RemoteRelayR1
Relay R1 working status
34
RemoteRelayMode.RemoteRelayR2
Relay R2 working status
35
RemoteRelayMode.RemoteRelayR3
Relay R3 working status
36
RemoteRelayMode.RemoteRelayR4
Relay R4 working status
37
RemoteRelayMode.RemoteRelayR5
Relay R5 working status
Register: DeviceAlarms
bit
7
6
5
4
3
2
1
0
-
-
-
-
-
-
SF
CA
Bit number
Mnemonics
Description
7..2
-
Reserved
1
SF
Permanent activation (damage) of the bay unit optical sensor
0
CA
Lack of communication with bay units, address collision or no bay unit has been registered
Register: DeviceEvents
bit
7
6
5
4
3
2
1
0
-
-
-
AS3
AS2
AS1
SS
UL
Bit number
Mnemonics
Description
7..5
-
reserved
4
AS3
Tripping in zone S3
3
AS2
Tripping in zone S2
2
AS1
Tripping in zone S1
1
SS
Optical module of the bay unit activation
0
UL
Activation of the voltage module U< of the central unit
Register: RelayState
bit
7
6
5
4
3
2
1
0
-
R7
R6
R5
R4
R3
R2
R1
Bit number
Mnemonics
Description
7
-
reserved
6..0
R[7..1]
Logical state of the executive relay R[7..1]
Relay R7 performs a signal function. Its value 1 has the meaning of the system efficiency.
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...