Page | 21
Select the main switches according to the next table:
Model
Power source
Max.
current
CB
ELB
(no. poles/A/mA)
Inv. R 8-12
220/240V~ /50Hz
21,5A
32 A
2(P+N)/32/30
Inv. R 5-18
220/240V~ /50Hz
33,2 A
40 A
2(P+N)/40/30
Inv. R 5-18
400V~/ 50Hz
12,5 A
25 A
4 (3F+N)/25/30
CB
– Circuit breaker; ELB – Earth leakage breaker.
15.11
Room thermostat installation
The simplest way to improve and control the comfort level of your installation
is through an ambient thermostat.
Your installation location is extremely important, following a series of
requirements as we can see in the figure below.
The thermostat must be installed:
•
an interior wall about 1.5m from floor level
•
a place where the temperature is uniform.
•
a place where have a good circulation of air around the thermostat.
The thermostat cannot be installed:
•
in exterior walls.
•
near the radiators, convectors, etc.
•
behind or near the doors.
•
near to the windows.
WARNING:
The room thermostat contact must be free of tension.
Connecting a tension on this contact will cause destruction of the controller.