background image

Metacentre DX Box 

 

 

Page 5

 

Compressor Status: 
 

 Compressor 

Running 

 

Compressor On Load 

  Flashing - Not Responding, Compressor 

Not Running When required to load. 

 

Service Maintenance function active 

  Pressure Limit Exceeded 

 

1: Compressor Alarm 

 

2: Auxiliary Alarm input active 

 

3: Pressure Sensor fault (display “- - - -

“) 

  1: Compressor Not Available 

 

2: Auxiliary Trip input active 

 

2.2 Indicators 

 
Run Indicator (Green LED) 
 
   

OFF  

DX Box Fault condition 

   ON 

 

Active 

 
Fault Indicator (Red LED) 
  
   

OFF – No fault 

 Slow 

Flash: 

 

1: Compressor Alarm 

 

2: Pressure Sensor fault (display “- - - -

“) 

 Fast 

Flash: 

 

1: Compressor Not Available 

 

2.3 Compressor 

Identification 

 
Each compressor connected to the DX Box 
will have an assigned compressor 
identification number #1 or #2. 
 

1

2

#1

DX Box

3

#2

 

 

The DX Box ‘group’ will also have a single 
unique system address identification and will 
be represented on the system management 
unit as a single entity using the ‘address’ 
identification number. The identification 
number will be unique for the system. 
 
For example, “C.03.1” indicates that the 
compressor is connected to the DX Box as 
compressor #1 and the DX Box is represented 

on the system management unit as 
compressor number “03”. 
  

2.4 Operation 

 
The DX Box is always active (started) and 
cannot be stopped. The DX Box will 
automatically switch between ‘Remote’, when 
under system management unit control, or 
‘Local’ mode.  
 

2.5  Power Failure Auto-Restart 

 
The DX Box will always automatically start 
when power is re-applied after a power supply 
disruption or failure. 
 

2.6 Failure 

Modes 

 
If communications with the system 
management unit is disrupted, the DX Box will 
switch to ‘Local’ mode and pressure regulation 
control is maintained using the set pressure 
set points. 
 
The DX Box will automatically switch back to 
‘Remote’ mode when communications with the 
system management unit are re-established, 
or the DX Box fault is reset. 
 
If a fault occurs with the DX Box, or power to 
the DX Box is disrupted, pressure regulation 
control is automatically transferred back to 
each compressor. The compressor(s) will 
continue to operate using the pressure 
settings programmed or set in the individual 
compressor controller(s). 
 

 The design of some air compressor control 

systems may inhibit automatic transfer of 
pressure regulation control to local operation 
mode. In this instance the compressor will not 
continue production of compressed air – 
consult the air compressor manual or your air 
compressor supplier / specialist for details 
before installing the DX Box unit. 
 

2.7 Compressor 

Fault 

 

If a compressor fault condition is detected the 
‘status’ display will show an ‘Alarm’ condition. 
The ‘status’ display associated with the 
compressor will also indicate a fault condition 
(see Status Symbols). The DX Box ‘Fault’ 
indicator (10) will flash to attract attention. 
Compressor fault conditions will also be 
communicated to the system management unit 
controller. 
 

Summary of Contents for metacentre DX Box

Page 1: ...MANY0739A GB Metacentre DX Box User Manual TM DX Box bar...

Page 2: ...tatus Symbols 2 4 Indications 2 5 Compressor Identification 2 6 Operation 2 7 Power Failure Auto Restart 2 8 Failure Modes 2 9 Compressor Fault 2 10 DX Box Fault 2 11 Pressure Sensor Fault 3 0 Parts L...

Page 3: ...6 wire cable and a compressor interface PCB i PCB The i PCB connections are identical to an system management unit The DX Box also provides optional local pressure sensor connections The compressor de...

Page 4: ...change from time to time dependant on the set sequencing mode of the management unit In Top Up mode the DX Box will allow variable capacity control as described above dependant on demand In Base Load...

Page 5: ...esented on the system management unit as compressor number 03 The status of the compressor will also be show using the Run and Load symbols If the Delivery pressure sensor option for a compressor has...

Page 6: ...Local mode 2 5 Power Failure Auto Restart The DX Box will always automatically start when power is re applied after a power supply disruption or failure 2 6 Failure Modes If communications with the sy...

Page 7: ...ontroller inputs and outputs E 0135 BAR System Pressure Sensor Fault If one of these fault conditions occur the DX Box will switch off The Run Indicator 9 will also switch off and the Fault Indicator...

Page 8: ...tem Part No Description 5 Y04CM59 00 Unit i PCB Optional Accessories Item Part No Description 6 Y04CM29 00 Sensor Pressure 4 20mA 0 16 0bar 7 Y01ENER35 00 Module Relay 24Vac 4 0 Technical Data Dimensi...

Page 9: ...3 C024 C025 C032 C030 C031 4 20mA Pressure 1 4 20mA SystemPress Ai3 VDC notused Aux Fault 2 Aux Output V1 8 10 12 X02 11 9 7 V2 C028 C029 C026 C027 X04 notused C015 C025 C024 10k 10k C016 C023 C013 C0...

Page 10: ...115V 24Vac 1 isolated 24Vac 2 earthed E E L N N L E BLUE BROWN RED GREEN VIOLET WHITE ORANGE BLACK FH1 FH2 FH3 FH4 FH5 1 VOLTAGE SELECT 2 3 4 X04 2 1 2 X03 X02 X01 T3 15A T1 6A T1 6A T1 0A T1 0A 1 2...

Reviews: