Metacentre DX Box 

 

 

Page 3

 

1.3.2 Automatic Mode (Ar) 
 

#1

#2

65%

35% = 100%

0%

-

-

35%

-

B

65%

A

-

100% A

B

A

B

 

 
Automatic mode can be used when the 
compressor capacities are different. The DX 
Box will utilise each compressor as required to 
match output to demand. This mode enables 
the compressor ‘group’ to behave in the same 
manner as a single (multiple step) variable 
output unit. 
 
The set ‘Interval Time’ is ignored in this mode, 
the DX Box will continuously evaluated 
utilisation to match demand. 
 
For example: 
 
If demand can be satisfied by the smaller of 
the two compressors (demand < 36%) the DX 
Box will utilise the lower capacity compressor 
(B). If demand increases above the output 
capacity of the smaller compressor, but within 
the capacity of the larger capacity compressor, 
the DX Box will utilise the larger capacity 
compressor (A). If demand exceeds to 
capacity of the larger capacity compressor the 
DX Box will load the larger compressor 
continuously and utilise the smaller capacity 
compressor to regulate as required. 
 
1.3.3 Management System Integration 
 
When integrated with a system management 
unit the DX Box compressor ‘group’ will 
respond in ‘Top-Up’ mode or ‘Base-Load’ 
mode as dictated by the management unit. 
The assigned mode of response will change 
from time-to-time dependant on the set 
sequencing mode of the management unit. 
 
In Top-Up’ mode the DX Box will allow 
variable capacity control (as described above) 
dependant on demand. 
 
In ‘Base-Load’ mode the DX Box will fully load 
both compressors to provide full base-load 
capacity output. 
 

The DX Box ‘group’ unit should be set as a 
variable output unit on the management 
system. The management system will fully 
utilise the variable output capacity capability of 
the DX Box ‘group’ and report the percentage 
of utilisation of the ‘group’ in the same manner 
as a single variable output compressor. 
 
1.3.4 Percentage Capacity 
 
The capacity of each compressor is 
expressed, and set, as a percentage of the 
combined output capacity of both 
compressors. 
 
For example: 
 
If the larger compressor #1 (A) has an output 
capacity of 13.0m

3

/min, and the smaller #2 (B) 

compressor an output capacity of 7.0m

3

/min, 

the total combined output of the DX Box 
‘group’ equates to 20.0m

3

/min. 

 
Total Capacity (20.0m

3

/min.) = 100% 

Compressor #1 (A) = 65% 
Compressor #2 (B) = 35%  
 
1.3.5 Compressor Failure Mode 
 
If one compressor in the DX Box ‘group’ 
suffers a shutdown failure, or is manually 
stopped, the DX Box will indicate an ‘Alarm’ 
condition. The remaining compressor will 
continue to function and the DX Box will 
continue to operate at reduced capacity. 
 
If both compressors suffer a shutdown failure, 
or are manually stopped, the DX Box will 
indicate a shutdown ‘Trip’ condition.  
 

Summary of Contents for metacentre DX Box

Page 1: ...MANY0739A GB Metacentre DX Box User Manual TM DX Box bar...

Page 2: ...tatus Symbols 2 4 Indications 2 5 Compressor Identification 2 6 Operation 2 7 Power Failure Auto Restart 2 8 Failure Modes 2 9 Compressor Fault 2 10 DX Box Fault 2 11 Pressure Sensor Fault 3 0 Parts L...

Page 3: ...6 wire cable and a compressor interface PCB i PCB The i PCB connections are identical to an system management unit The DX Box also provides optional local pressure sensor connections The compressor de...

Page 4: ...change from time to time dependant on the set sequencing mode of the management unit In Top Up mode the DX Box will allow variable capacity control as described above dependant on demand In Base Load...

Page 5: ...esented on the system management unit as compressor number 03 The status of the compressor will also be show using the Run and Load symbols If the Delivery pressure sensor option for a compressor has...

Page 6: ...Local mode 2 5 Power Failure Auto Restart The DX Box will always automatically start when power is re applied after a power supply disruption or failure 2 6 Failure Modes If communications with the sy...

Page 7: ...ontroller inputs and outputs E 0135 BAR System Pressure Sensor Fault If one of these fault conditions occur the DX Box will switch off The Run Indicator 9 will also switch off and the Fault Indicator...

Page 8: ...tem Part No Description 5 Y04CM59 00 Unit i PCB Optional Accessories Item Part No Description 6 Y04CM29 00 Sensor Pressure 4 20mA 0 16 0bar 7 Y01ENER35 00 Module Relay 24Vac 4 0 Technical Data Dimensi...

Page 9: ...3 C024 C025 C032 C030 C031 4 20mA Pressure 1 4 20mA SystemPress Ai3 VDC notused Aux Fault 2 Aux Output V1 8 10 12 X02 11 9 7 V2 C028 C029 C026 C027 X04 notused C015 C025 C024 10k 10k C016 C023 C013 C0...

Page 10: ...115V 24Vac 1 isolated 24Vac 2 earthed E E L N N L E BLUE BROWN RED GREEN VIOLET WHITE ORANGE BLACK FH1 FH2 FH3 FH4 FH5 1 VOLTAGE SELECT 2 3 4 X04 2 1 2 X03 X02 X01 T3 15A T1 6A T1 6A T1 0A T1 0A 1 2...

Reviews: