- 2 -

Sizing

Mop Sink Sizing Guide

Size

LPS

US/GPM

2”

84

22

3”

142

37.5

4”

170

45

Floor Drains & Floor Sinks

Take the volume of water produced by the 

number of hose bibbs (ie 1.5-2.0 gpm per 3/4” 

faucet). ASPE also recommends using 4gpm 

floor drain if you cannot use the bibb method.

Table A - Procedure for Sizing Grease Interceptors

STEP

FORMULA

EXAMPLE

1

Determine cubic content of fixture by multiplying length x 

width x depth

A sink 24” long by 20” wide by 12” deep.

Cubic content: 24 x 20 x 12 = 5,760 cubic inches

(61.0 x 50.8 x 30.48 cm

3

 )

2

Determine capacity in gallons. 

1 gallon = 231 cubic inches

Contents in gallons:

5,760 / 231 = 24.9 gallons

(94,451.42 / 1,000 = 94.45 litres)

3

Determine actual drainage load.

 

The fixture is normally filled to approximately 75% of capacity 

with water as the items being washed displace about 25% of 

the total fixture content.

Actual drainage load = 75% of fixture capacity

Actual drainage load:

.75 x 24.9 = 18.7 gallons

(0.75 x 94.45 = 70.84 litres)

4

Determine flow rate and drainage period.

In general, good practice dictates a one minute drainage pe-

riod; however, where conditions permit, a two minute drainage 

period is acceptable. Drainage period is defined as the actual 

time required to completely drain the fixture.

Flow rate = Actual Drainage Load

                      Drainage Period

Calculate flow rate for one minute drainage period:

18.7 / 1 = 18.7 g.p.m. flow rate

(70.84 / 1 min. = 70.84 l.p.m.)

Calculate flow rate for two minute drainage period:

18.7 / 2 = 9.4 g.p.m. flow rate

(70.84 / 2 min. = 35.42 l.p.m.)

5

Select Interceptor.

From Table B select the interceptor with a flow rating at least 

equal to the calculated flow rate. When the calculated flow rate 

falls between two sizes, select the larger of the two 

interceptors.

For a one minute drainage period:

18.7 g.p.m. (70.84 l.p.m.) flow rate = 20 g.p.m. G.I.

For a two minute drainage period:

9.4 g.p.m. (35.42 l.p.m.) flow rate = 10 g.p.m. G.I.

Table B - Procedure for Sizing Grease Interceptors

PDI Size Symbol

4

7

10

15

20

25

35

50

Flow Rate US Gallons per Minute (GPM)

4

7

10

15

20

25

35

50

Flow Rate Liters per Second (LPS)

.25

.44

.63

.95

1.26

1.58

2.20

3.16

Grease Capacity Pounds (Lbs)

8

14

20

30

40

50

70

100

Grease Capacity Kilograms (Kgs)

3.63

6.35

9.07

13.61 18.14 22.68

31.75

45.36

Sampling Access

 
Some municipalities require a sampling port to monitor effluent quality. If 
the unit is on the floor, or semi-recessed into the floor, a cleanout tee can 
be installed downstream of the Grease Interceptor. If the unit is installed 
in the floor, a backwater with its flapper removed, makes an effective 
collection port. Like the FCD the backwater valve can be extended to 
finish floor level using a sleeve kit.

Venting

 
Grease Interceptors must have a vented waste, sized in accordance 
with local code requirements for venting interceptors to retain a 
water seal and prevent siphoning. Most codes dictate that two 
vents be installed, one upstream and one downstream of the 
grease interceptor. The upstream vent must not be placed between 
the air intake and the grease interceptor.

For Basic Grease Interceptor sizing, please reference the Sizing Guide or the Plumbing & 

Drainage Institute Standard PDI-G 101. Without a properly sized flow control, the flow 

through the interceptor may exceed the rating of the unit, causing lower efficiencies 

and allowing grease to pass through the interceptor into the downstream piping. Be 

careful that you do not confuse liquid capacity and flow capacity. Liquid capacity is 

rated in litres or gallons while flow capacity is rated in gpm (gallons per minute) or L/

sec (litres per second).
If sizing indicates that a larger Grease Interceptor is required, you maybe able to 

compromise to a smaller unit by adopting to a 2 minute drain down time in your 

sizing calculation. Although the smaller unit will be less expensive, the grease 

capacity of a smaller unit will dictate the cleaning frequency required.

For additional Sizing Tools and Maintenance Interval 

Optimization, use our Endura® Calculator online or 

email:

  

[email protected]

   Calculator

Summary of Contents for Endura 10

Page 1: ...GRAVE En tant qu accessoire de plomberie votre intercepteur de graisse Endura DOIT tre isol du syst me de drainage advenant qu on doive proc der un essai final du drain ou tout autre essai de pressio...

Page 2: ...izing Grease Interceptors PDI Size Symbol 4 7 10 15 20 25 35 50 Flow Rate US Gallons per Minute GPM 4 7 10 15 20 25 35 50 Flow Rate Liters per Second LPS 25 44 63 95 1 26 1 58 2 20 3 16 Grease Capacit...

Page 3: ...coulement de 2 minutes D bit de 9 4 gal min 35 42 L min intercepteur de graisse de 10 gal min Tableau B Dimensionnement des intercepteurs de graisse Symbole dim PDI 4 7 10 15 20 25 35 50 D bit Gal US...

Page 4: ...9 07 13 61 18 14 22 68 31 75 45 36 Acceso a toma de muestras Algunos municipios exigen un puerto de muestreo para controlar la calidad de emisi n Si la unidad est sobre el piso o semiempotrada dentro...

Page 5: ...e graisse et l intercepteur est non prot g et constitue un site potentiel d accumulation de graisse Les installations n cessitant de grandes longueurs de tuyauteries pour atteindre l intercepteur pr s...

Page 6: ...os lavaplatos Para evitar que detergentes industriales comprometan y tengan impacto en el desempe o del sistema se recomienda instalar un interceptor de grasa aparte para cada lavavajillas comercial E...

Page 7: ...n seul r gulateur de d bit devrait tre utilis Le dispositif de contr le de d bit peut tre encastr dans le plancher au besoin Des manchons d extension sont disponibles afin d obtenir une bonne finition...

Page 8: ...lancher Connexions indirectes Intervalle d air coupure d air Dans certains endroits il est exig que les installations de plonge soient faites sur une base indirecte avec une coupure anti retour Cette...

Page 9: ...ur de d gagement minimum de 15 po 21 po Altura m nima de espacio libre 15 21 Grease Interceptor Intercepteur de graisse Interceptor de grasa Air Intake Prise d air Entrada de aire Sink vier Fregadero...

Page 10: ...n installing in floor the interceptor must have both the cover fitted and be filled with water to the inlet outlet level This will ensure the tank itself will not move during backfilling pouring and o...

Page 11: ...a7 4 4 3 9 deOntario Canad Instalaci nt pica L utilisation d un seul intercepteur de graisse pour plusieurs installations n est recommand que si les installations sont proches les unes des autres un...

Page 12: ...r precauciones para rellenar de manera uniforme alrededor de la unidad s lo con una ligera presi n manual Los conjuntos de extensi n est n disponibles para todos los modelos y para el dispositivo de c...

Page 13: ...avant livraison non incluse Cubierta de reemplazo con pestillos placa PDI no incluida 3910A 2ARPL 3 Cover gasket Joint en n opr ne Junta de hule 3910A 5 4 Removable Outlet Baffle D flecteur de sortie...

Page 14: ...usse de verrouillage de rechange 4 loquets droits et gauches et axes Kit de reemplazo de pestillos 4 IZQ 4 DER pestillos y pasadores 3935A 6RPL 2 Replacement cover with latches PDI plate not included...

Page 15: ...ompact Flow Control device where it is preferred or required for in floor installation of the flow control Un ensemble de r gulateur en PVC de 2 po avec entr e d air optionnel peut tre achet s par men...

Page 16: ...lb kg Capacit de graisse r elle enregistr e la d gradation lors d un essai conforme la norme ASME A112 14 3 Endura7 Endura10 Endura15 Endura20 Endura25LO Endura25 Endura35 Endura50 PartNumber 3907A02...

Page 17: ...n et l limination de d chets la s paration et le stockage de mati res l utilisation et la manutention de produits de nettoyage l entretien les avantages d adh rer au code et aux meilleures pratiques d...

Page 18: ...a entrada la salida y en el puerto de desviaci n de la purga de aire Para el Endura de 50 GPM se puede aplicar una delgada capa de sellador de silicona a los rieles del deflector de salida luego de su...

Page 19: ...a los servicios de una empresa de reciclado para el aceite de cocer usado Este aceite puede ser reciclado para fabricar productos tiles tales como jab n alimentos para animales y productos de biodi se...

Page 20: ...laza el mantenimiento de rutina de remoci n de los s lidos alimentarios Debe usarse un interceptor de s lidos junto con un sistema autom tico de inyecci n de bacterias Endura recomienda seleccionar un...

Page 21: ...ssous Registro de servicio del interceptor de grasa Registro Deber llevarse un registro escrito de todas las actividades de mantenimiento limpieza e inspecci n efectuadas en el interceptor de grasa de...

Page 22: ...ultant d un vice de fabrication de mat riaux ainsi que la perforation de l intercepteur s il est utilis en conditions normales Le fabricant n offre pas de garantie contre les perforations r sultant de...

Page 23: ...23 Notes Remarques Notas...

Page 24: ...lle de l intercepteur de graisse install Cu l es el tama o del interceptor de grasa instalado 7gal min 0 44L s 10gal min 0 63L s 15gal min 0 94L s 20gal min 1 26L s 25gal min 1 6L s 35gal min 2 2L s 5...

Reviews: