Status at:
February 2013
ESE 807 / 1107 / 1307 / 1407 DBG (ES) DIN
49
Fig. 5-1: FI protection switch
1.
The generator must have been started (see 4.4).
2.
Put the protection switch
(seeFig. 5-1 -(20))
into position 1.
3.
Activate the test switch
(seeFig. 5-1 (10))
.
The switch position displays the result
(seeFig. 5-1 (20))
:
Symbol
Significance
Position I
Switch does not trigger. FI protection switch is defec-
tive.
Position 0
Switch triggers. FI protection switch is working proper-
ly.
Table 5.1: FI protection switch test
The device has been tested in compliance with DIN VDE
0100-551.
Checking the FI protection
switch: