Operating Instructions

TMT122 DIN rail 

iTEMP

® 

 HART

® 

Temperature Transmitter

Summary of Contents for TMT122

Page 1: ...BA155R 24 ae 10 04 51006562 Operating Instructions TMT122 DIN rail iTEMP HART Temperature Transmitter...

Page 2: ...Temperature DIN rail transmitter 2 Endress Hauser...

Page 3: ...Communicator DXR 275 375 14 5 1 2 COMMUWIN II operating program 15 6 Commissioning 16 6 1 Installation and function check 16 6 2 Commissioning 16 6 2 1 Quick Setup 16 6 2 2 Configuration with HART pro...

Page 4: ...reserves the right to change and or improve the product design and specifications without notice Warning Failure to follow these installation guidelines could result in death or serious injury Make s...

Page 5: ...escription of the unit functions A complete description of all the functions as well as a detailed overview of the function matrix can be found in this chapter Quick Setup Fast entry into the unit con...

Page 6: ...ction schematics Due to its construction the transmitter cannot be repaired When disposing of the DIN rail transmitter please take note of the local disposal regulations Electrical temperature sensors...

Page 7: ...in these operating instructions are followed The safety notes in these instructions are highlighted using the following symbols Note This icon indicates activities and actions that if not followed cor...

Page 8: ...ion in which they are safe to operate The devices comply with the applicable stan dards and regulations in accordance with IEC61010 Protection Measures for Electrical Equipment for Measurement Control...

Page 9: ...122 Operating instructions Control drawing for use in hazardous areas 3 Installation 3 1 Installation conditions Installation conditions Caution The unit must only be powered by a power supply that op...

Page 10: ...r threads with silicone tape Screw the sensor 2 into the thermowell 1 Install drain seals if required for harsh environments or to satisfy code requirements Screw the connection head 4 to the sensor a...

Page 11: ...mowell before applying any pressure Attach and connect appropriate lengths of sensor lead wire from the connection head to the sen sor terminal block Tighten the connection head cover Enclosure covers...

Page 12: ...nd power supply Connect the cable wires from the power supply to terminal 1 and 2 according to the wiring diagram see fig 5 For convenient installation the connection is designed as a removable plug s...

Page 13: ...in combination with a PC E H operating software Commuwin II a Commubox FXA 191 connected to the communication sockets of a power supply unit b Loop power supply e g RNS 221 power supply or RN 221N ac...

Page 14: ...rail transmitter is set up using the HART protocol The values measured can also be read using the HART protocol In order to do this the user has two possibi lities Operation using a universal hand ope...

Page 15: ...of the type of unit and communication mode HART or PROFIBUS Commuwin II offers the following functions Setting up unit functions Visualization of measured values Data security of unit parameters Unit...

Page 16: ...S EXPANDED Windows 2000 Select Advanced settings for COM1 from the START SETTINGS SYSTEM CONTROL SYSTEM HARDWARE DEVICE MANAGER CONNECTIONS COM and LPT COMMUNICATION CONNECTION COM1 CONNECTION SETTING...

Page 17: ...trix Parameter This matrix systematically contains all HART accessible functions 2 Using Matrix Parameter the function group can be selected e g basic calibration and then followed by the required fun...

Page 18: ...win II operating program is possible independent of the type of unit and communication mode HART or PROFIBUS Commuwin II offers the following func tions Setting up unit functions Display Data security...

Page 19: ...Endress Hauser 19 Commuwin II operating matrix fig 10 Commuwin II operating matrix A Unit functions active only on customer specific linearization B Unit functions active only on TC connection C Unit...

Page 20: ...re deviation are entered in the SMC 32 Pressing the CALCU LATE key calculates the linearization and OK adopts it into ReadWin 2000 Linearization coefficients X0 to X4 are entered into the COMMUWIN II...

Page 21: ...the internal comparison measurement point Note Display 7 digit number with floating decimal point and engineering unit e g 23 70 C 71 04 F a a Only for Commuwin II operating matrix Time filter V0H2 D...

Page 22: ...1200 C 2192 F Type K 270 C 454 F 1372 C 2501 F Type L 200 C 328 F 900 C 1652 F Type N 270 C 454 F 1300 C 2372 F Type R 50 C 58 F 1768 C 3214 F Type S 50 C 58 F 1768 C 3214 F Type T 270 C 454 F 400 C...

Page 23: ...first coefficient for customer specific linearization polynome 4th grade with five coefficients see chapter 6 2 4 Coefficient X1 V3H1 Input COEFFICIENT X1 see chapter 6 2 4 Coefficient X2 V3H2 Input...

Page 24: ...imulation mode Entry Off On Off Current out sim V9H8 Entry of simulation value current Entry 3 58 to 21 7 mA Security locking V9H9 Release code for setting up Entry Lock 0 Release 281 281 Function gro...

Page 25: ...5 Read primary variable output information r 16 Read final assembly number r 17 Write message w 18 Write tag descriptor date w 19 Write final assembly number w Common practice 34 Write primary variabl...

Page 26: ...the internet from the following address www readwin2000 com Please contact your supplier when ordering 9 Trouble shooting 9 1 Trouble shooting instructions If faults occur after commissioning or duri...

Page 27: ...Defective DIN rail transmitter Replace DIN rail transmitter Fault Cause Action cure Fault current 3 6 mA or 21 mA Defective sensor Check sensor Incorrect RTD connection Reconnect cables correctly conn...

Page 28: ...sensor Replace sensor Programming Sensor type RTD setup set up cor rect thermocouple Incorrect 2 wire connection current loop Connect the cables correctly see connection diagram Defective DIN rail tra...

Page 29: ...d voltage transmitters Setup of the TMT 122 is done using the HART Protocol with hand operating module DXR 275 375 or PC COMMUWIN II or Read Win 2000 operating software 10 2 Input Measured variable Te...

Page 30: ...e transmitter Resistance 10 to 400 10 to 2000 10 100 Thermocouples TC to NIST Monograph 175 IEC 584 to ASTM E988 to DIN 43710 Type B PtRh30 PtRh6 a Type E NiCr CuNi Type J Fe CuNi Type K NiCr Ni Type...

Page 31: ...please see control drawing Residual ripple Allowable ripple Uss 3 V at Ub 13 V fmax 1 kHz 10 5 Performance characteristics Response time 1 s Reference operating conditions Calibration temperature 73...

Page 32: ...n Td 50 ppm K max span 50 ppm K calibrated span Influence of load 0 02 100 Values refer to the full scale value Long term stability 0 18 F year 0 1 C year or 0 05 year Values under reference operating...

Page 33: ...r IEC 61326 Amendment 1 1998 and NAMUR NE 21 This recommendation is a uniform and practical way of determining whether the devices used in laboratory and process control are immune to interference wit...

Page 34: ...cold junction compensation of wire resistance with 2 wire connection failure mode output signal 4 to 20 20 to 4 mA digital filter damping offset TAG descriptor 8 16 characters output simulation custom...

Page 35: ...RS 21 G GL German Lloyd marine approval 8 H HART function matrix 18 HART hand operating module DXR 275 375 13 HART protocol 14 Hazardous areas 7 Head transmitter 9 I Installation angle 9 Installation...

Page 36: ...Index Temperature DIN rail transmitter 36 Endress Hauser...

Page 37: ...ll 800 668 3199 Please be sure to include the following information when requesting a Return Authorization number This information will help us speed up the repair and return process Customer name Cus...

Page 38: ...BA155R 24 ae 10 04 51006562 FM SGML6 0 2004 Endress Hauser Inc...