9 Trouble-shooting
Temperature DIN rail transmitter
28
Hauser
Application faults for TC connection
9.4
Returns
Returns
Please follow the return Authorization Policy at the end of these instructions.
9.5
Disposal
Disposal
Due to its construction, the DIN rail transmitter cannot be repaired. When disposing of the DIN rail
transmitter please take note of the local disposal regulations.
Fault
Cause
Action/cure
Fault current
(
≤
3.6 mA or
≥
21 mA)
Sensor incorrectly connected
Connect sensor correctly to
terminal plan (polarity)
Defective sensor
Replace sensor
Programming
Sensor type ’RTD’ setup; set up cor-
rect thermocouple
Incorrect 2 wire connection (current
loop)
Connect the cables correctly (see
connection diagram)
Defective DIN rail transmitter
Replace DIN rail transmitter
Measured value incorrect/inaccurate
Faulty sensor installation
Install sensor correctly
Heat conducted via sensor
Take note of sensor installation
length
Transmitter programming faulty (scale)
Change scale
Incorrect thermocouple setup
Change parameter ‘Sensor type’
Incorrect cold junction setup
See chapter ‘Operation’ and ‘Techni-
cal data’
Offset incorrectly set up
Check offset
Fault on the thermowell welded
thermo wire (coupling of interference
voltages)
Use sensor where the thermo wire is
not welded