24
Soliwave FDR16/FQR16
Hauser
Operation options
7.4.3
Set process window
•
If the point level cannot be reliably detected after an automatic adjustment because the
medium to be detected does not dampen sufficiently, the process window must reduced
step by step.
• An enlargement of the process window is also possible. This is useful if, for example,
material is conveyed through the detection range of the microwave barrier due to the
process, which leads to attenuation of the microwave.
Customize process window
Operating magnet on "
Process Window
":
→ green LED flashes quickly
→ display (5 s) current process window
Continue to stop operating magnet → every 5 s change to next process window
Remove operating magnet → last displayed process window selected
Display
Meaning
100 %
(for very good damping media)
70 %
(for good damping media)
50 %
(factory setting)
30 %
(for smaller damping media)
15 %
(for small damping media)
7.4.4
Set switching delay
A switching delay is helpful, for example, if the signal strength fluctuates strongly, so that
the outputs only switch when the switching point is exceeded or undershot for a corre-
spondingly long time.
Set switching delay
Operating magnet on "
Switch Delay
":
→ green LED flashes quickly
→ display (5 s) current switching delay
Continue to stop operating magnet → every 5 s change to next switching delay
Remove operating magnet → last displayed switching delay selected
Display
Meaning
Switching delay off
(factory setting)
500 ms
1 s
5 s
10 s