Soliwave FDR16/FQR16
Hauser
23
Operation options
7.3
On-site operation
0000000011
23 On-site operation
Operation via operating magnet → 29
To operate, place the operating magnet (north pole visible as shown) on the marked areas
of the FDR16. The operating magnet is included in the scope of delivery of the FDR16. It
can be optionally cancelled or ordered as an accessory.
7.4
Parameterization
Setting options only available with activated parameterization mode (7.4.2 ... 7.4.5)
7.4.1
Activation parameterization mode
Power supply off: Operating magnet on "
Auto Span
", "
Process Window
" or "
Switch
Delay
"
Power supply on: Initialization → green LED (operation) flashes slowly
Remove operating magnet → parameterization mode (green LED continues to flash
slowly)
• The device continues to operate normally in the background depending on the current
settings, so that, for example, exceeding the point level leads to a switchover of the
signal output.
•
10 minutes no action → parameterization mode is terminated (device switches to nor
-
mal operation)
• The parameterization mode can also be terminated by a voltage reset.
7.4.2
Automatic adjustment
• Automatic adjustment of the process-dependent detection range.
• To be performed once during commissioning
with free path
Perform automatic adjustment
Operating magnet on "
Auto Span
" → green LED flashes quickly
Remove the operating magnet within 10 seconds:
→ green LED lights up for 2 s
→ automatic adjustment successfully performed
•
Automatic adjustment not feasible (for example, with covered path) → warning
•
After an automatic adjustment, the white LED (signal strength) lights up permanently if
the signal strength is sufficiently high and there is a free path.
• When the path is covered, the yellow LED (sensor status) indicates the covered path,
and the white LED is off or flashing at a low frequency. If this is not the case, the process
window must then be adjusted.