background image

Solitrend MMP60

Diagnostics and troubleshooting

Hauser

19

Moisture scaling set incorrectly in the PLC

In the device, 0 to 20 % moisture corresponds to the current output of 0 to 20 mA or

4 to 20 mA.

Enter the 0 to 20 % moisture scaling in the PLC.
 Contact the PLC manufacturer

The calibration curves that are saved do not match the material

In the case of materials where the slope does not roughly correspond to a calibration curve

saved in the device, a 2-point calibration (dry and wet material sample) may be necessary in

the PLC or sensor.

 SD02333M 

Remote display

 - Description of operation and material calibration

Moisture value too high

In the case of coarse-grained or hydrophobic materials, water can escape directly onto the

measurement surface and therefore cause a high moisture value.

Enter limit values in the PLC.
 Contact the PLC manufacturer

Incorrect data processing

In the event of inaccurate data processing, check the moisture value displayed in the PLC.

1. Connect the device to the remote display
2. Compare the moisture value shown in the PLC with the moisture value shown on the

display

3. For a test run, set the 

CS

 operating mode in the device

4. After the test run, set the operating mode back to 

CA

Start/stop conditions are not correct

• Start condition: time in seconds or kg in the scales

• Stop condition: usually % of target weight

Check the start/stop conditions in the PLC
 Contact the PLC manufacturer

If the solutions described here do not rectify the problem, contact the manufacturer's

Service Department.

Summary of Contents for Solitrend MMP60

Page 1: ...tructions they are not a substitute for the Operating Instructions pertaining to the device For detailed information refer to the Operating Instructions and other documentation Available for all devic...

Page 2: ...Solitrend MMP60 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Page 3: ...7 4 2 Product identification 7 4 3 Manufacturer s address 8 4 4 Storage transport 8 5 Mounting 8 5 1 Mounting requirements 8 5 2 Mounting the device 8 5 3 Post mounting check 9 6 Electrical connection...

Page 4: ...ollowing requirements Trained qualified specialists must have a relevant qualification for this specific function and task Personnel must be authorized by the plant owner operator Be familiar with fed...

Page 5: ...t Observe the limit values in the Technical data Incorrect use The manufacturer is not liable for damage caused by improper or non intended use Clarification of borderline cases With regard to special...

Page 6: ...ements has been tested and left the factory in a condition in which it is safe to operate It meets the general safety standards and legal requirements It also complies with the EU directives listed in...

Page 7: ...ditions is not met please contact the manufacturer s sales office 4 2 Product identification The device can be identified in the following ways Nameplate specifications Extended order code with breakd...

Page 8: ...lace of installation to ensure that the material flow and therefore the bulk density over the measurement surface is constant The measuring field of the device must be completely covered by material a...

Page 9: ...ns Unit of measurement mm in 5 2 1 Mounting the housing with the remote electronics module The housing with the remote electronics module can be mounted with two screws M5 163 6 42 52 2 05 8 0 3 1 A00...

Page 10: ...ured 6 Electrical connection 6 1 Connecting requirements 6 1 1 Cable specification Connecting cables with a pre assembled 10 pin socket on the device side are available in different standard lengths 4...

Page 11: ...WH G RS485 B must be enabled Wire color brown BN C IMP Bus RT Wire color gray GY pink PK see figure below J IMP Bus COM Wire color blue BU red RD see figure below K 2nd analog positive Wire color pin...

Page 12: ...g output The device can be set to 0 to 20 mA or 4 to 20 mA The current output can also be set inversely to 20 to 0 mA or 20 to 4 mA for special controllers and applications The analog outputs can be s...

Page 13: ...10 0 to 20 or 0 to 30 8 1 1 Possible settings There are several possible settings for the analog outputs Analog outputs Options 0 to 20 mA 4 to 20 mA The current output can also be set inversely for...

Page 14: ...setting is saved to the non volatile memory of the device 8 2 1 Operating mode The device is supplied from the factory with the CH mode for applications in the construction industry and with the CA mo...

Page 15: ...o discharge hatch The CH mode performs filtering automatically This allows drip water that forms in the silo to be filtered out of the measured value for example 8 3 Calibration curve set A for genera...

Page 16: ...6 Calibration curve set A Cal 1 Cal 2 Cal 3 Cal 4 Cal 5 Cal 6 Cal 7 Cal 10 Cal 11 H Gravimetric moisture t Radar transit time picoseconds 1 Cal 1 Universal sand gravel grit 2 Cal 2 Sand 1 6 3 Cal 3 S...

Page 17: ...urves Cal 1 to Cal 15 for various materials that are saved and can be selected in the device The gravimetric moisture H is indicated as a percentage on the y axis and the associated radar transit time...

Page 18: ...el shift offset in the PLC The parameter has different names depending on the PLC e g initial load zero point offset measuring range etc Perform a parallel shift offset in the PLC Contact the PLC manu...

Page 19: ...se grained or hydrophobic materials water can escape directly onto the measurement surface and therefore cause a high moisture value Enter limit values in the PLC Contact the PLC manufacturer Incorrec...

Page 20: ...www addresses endress com 71550111 71550111...

Reviews: