Soliphant with
electronic insert FEM 44
Universal power version with one relay output
Power supply:
Alternating current 19 V ... 250 V, 16 Hz ... 60 Hz, or direct current 19 V ... 200 V.
Connect an isolating switch and (quick-acting) 0.2 A fuse next to the separate
housing.
Relay output:
1 potential-free changeover contact (SPDT).
For load on contact see Technical Data on Page 31.
On alarm and power failure:
– The relay contact breaks the connection between Terminal 4 and Terminal 3,
– The relay contact closes the connection between Terminal 4 and Terminal 5.
Protecting the relay contact:
– Connect a spark arrester when connecting a device with high inductivity
– Fine-wire fuse (dependent on the load connected)
Note:
For connecting an extra-low voltage circuit with reliable separation:
Total voltage for power supply and relay output max. 300 V.
Note!
PE
U~
5
3
4
1
2
a u r
L1 N
L+ L–
NO C NC
0,5 A
U–
…
Relay output
BA
175
Y21
Fig. 21
Wiring
Electronic insert FEM 44
for universal power supply;
relay output with one
potential-free changeover
contact (SPDT)
5 Electrical Connection
FTM 30 DR, FTM 31 DR, FTM 32 DR