RID16
Technical data
Hauser
37
10.0.2
Power supply
Electrical connection
a0011324
Abb. 17:
Terminal assignment of the field indicator.
Supply voltage
Voltage is supplied via the fieldbus.
U = 9 to 32 V DC, polarity-independent (max. voltage U
b
= 35 V).
Cable entry
The following cable entries are available:
• Thread NPT1/2
• Thread M16
• 2x adapter NPT1/2
• 2x gland M16
10.0.3
Installation
Installation instructions
Mounting location
Wall or pipe mounting (see 'Accessories')
Orientation
No restrictions, the orientation depends on the readability of the display.
10.0.4
Environment
Ambient temperature limits
-40 to +80 °C (-40 to 176 °F)
!
Note!
The display can react slowly at temperatures < -20 °C (-4 °F).
The readability of the display is no longer guaranteed at temperatures < -30 °C (-22 °F).
Storage temperature
-40 to +80 °C (-40 to 176 °F)
Altitude
Up to 4000 m (13100 ft.) above mean sea level in accordance with IEC 61010-1, CSA 1010.1-92
Climate class
According to IEC 60654-1, Class C