RID16
Technical data
Hauser
35
10
Technical data
10.0.1
Communication
• FOUNDATION Fieldbus™ H1, IEC 61158-2
• FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: supported baud rate = 31.25 kBit/s
• Signal coding = Manchester II
• LAS (link active scheduler), LM (link master) function is supported:
Thus, the indicator can assume the function of a link active scheduler (LAS) if the current link
master (LM) is no longer available. The device is supplied as a BASIC device. To use the device
as an LAS, this must be defined in the distributed control system and activated by downloading
the configuration to the device.
• In accordance with IEC 60079-27, FISCO/FNICO
Breakdown information
Status message as per FOUNDATION Fieldbus™ specification.
Mains voltage filter
50/60 Hz
Current consumption
≤
11 mA
Switch-on delay
8 s
Data of the FOUNDATION
Fieldbus interface
Basic data
Virtual communication relationships (VCRs)
Device Type
10CF (hex)
Device Revision
01 (hex)
Node Address
Default: 247
ITK Version
5.2.0
ITK Certification Driver No.
IT064000
Link Master-capable (LAS)
Yes
Link Master / Basic Device
selectable
Yes; factory setting: Basic Device
Number of VCRs
58
Number of Link Objects in VFD
64
Permanent Entries
58
Client VCRs
0
Server VCRs
5
Source VCRs
8
Sink VCRs
0
Subscriber VCRs
35
Publisher VCRs
10