Operation
Prothermo NMT532
50
Hauser
Spot temperature of the display array
When some temperature elements (resistance and material) are located in each input
cable in the probe; average calculation is performed based on sum of submerged
temperature element value/total number of temperature element submerged.
3
4
5
6
8
9
1
2
a
b
c
7
A0038609
35
Spot temperature
a
Gas (vapor phase)
b
Level
c
Liquid phase
1
NMT532
2
Converter
3
Pt100 element No.5: 2.45 °C (76.1 °F) (T5)
4
Pt100 element No.4: 24 °C (75.2 °F) (T4)
5
Pt100 element No.3: 26.0 °C (78.8 °F) (T3)
6
Pt100 element No.2: 25.5 °C (77.9 °F) (T2)
7
Pt100 element No.1: 25.0 °C (77.0 °F) (T1)
8
Input signal cable
9
Probe bottom
8.3.4
Element position 1: VH30 to VH35 (VH36 to VH39 are not
available in NMT 532)
Code
Display
Details
VH30-VH39
Position 1-10
(Element positions 1
to 10)
Item type
Read / Write
Range
0 to 99
999 mm
Displays individual temperature measurement elements.
Sets the element position from the bottom of the tank.
Calculation is automatically performed if "Equal" was selected as the
element interval in VH85. If "Unequal" was selected, all element
positions must be entered manually.