Proline Promass F 100 Modbus RS485
Diagnostics and troubleshooting
79
Diagnostic information
Diagnostic code
Status signal
Diagnostic number
Short text
↓
↓
↓
Example
A0013958
842
Process limit
3-digit number
12.3.2 Calling up remedy information
Remedy information is provided for every diagnostic event to ensure that problems can be
rectified quickly:
• On the home page
Remedy information is displayed in a separate field below the diagnostics information.
• In the
Diagnostics
menu
Remedy information can be called up in the working area of the user interface.
The user is in the
Diagnostics
menu.
1. Call up the desired parameter.
2. On the right in the working area, mouse over the parameter.
A tool tip with remedy information for the diagnostic event appears.
12.4 Diagnostic information via communication interface
12.4.1 Reading out diagnostic information
Diagnostic information can be read out via Modbus RS485 register addresses.
• Via register address
6821
(data type = string): diagnosis code, e.g. F270
• Via register address
6859
(data type = integer): diagnosis number, e.g. 270
For an overview of diagnostic events with diagnosis number and diagnosis code
12.4.2 Configuring error response mode
The error response mode for Modbus RS485 communication can be configured in the
Communication
submenu using 2 parameters.
Navigation path
Setup → Communication