System integration
Proline 500 PROFINET
56
Hauser
Discrete Output module
Transmit discrete output values from the automation system to the measuring device.
Assigned device functions
Slot
Device function
Status (meaning)
16
Flow override
• 0 (disable device function)
• 1 (enable device function)
18…20
Relay output
Relay output value:
• 0
• 1
Heartbeat Verification module
Receive discrete output values from the automation system and transmit discrete input values
from the measuring device to the automation system.
The Heartbeat Verification module receives discrete output data from the automation system
and transmits discrete input data from the measuring device to the automation system.
The discrete output value is provided by the automation system in order to start Heartbeat
Verification. The discrete input value is depicted in the first byte. The second byte contains
status information pertaining to the input value.
The discrete input value is used by the measuring device to transmit the status of the
Heartbeat Verification device functions to the automation system. The module cyclically
transmits the discrete input value, along with the status, to the automation system. The
discrete input value is depicted in the first byte. The second byte contains status information
pertaining to the input value.
Only available with the Heartbeat Verification application package.
Assigned device functions
Slot
Device function
Bit
Verification status
17
Status verification
(input data)
0
Verification has not been performed
1
Verification has failed
2
Currently performing verification
3
Verification terminated
Verification result
(input data)
Bit
Verification result
4
Verification has failed
5
Verification performed successfully
6
Verification has not been performed
7
–