Electrical connection
Proline 500 PROFINET
38
Hauser
Setting the device name
Risk of electric shock when opening the transmitter housing.
‣
Before opening the transmitter housing:
‣
Disconnect the device from the power supply.
The default IP address may
not
be activated .
1
2
3
4
5
6
7
8
128
64
32
16
8
4
2
1
N
ame of S
tat
ion
A0034498
‣
Set the desired device name using the corresponding DIP switches on the
I/O electronics module.
Setting the device name via the automation system
DIP switches 1-8 must all be set to
OFF
(factory setting) or all be set to
ON
to be able to set
the device name via the automation system.
The complete device name (name of station) can be changed individually via the automation
system.
• The serial number used as part of the device name in the factory setting is not saved. It
is not possible to reset the device name to the factory setting with the serial number.
The value "0" is used instead of the serial number.
• When assigning the device name via the automation system:
assign the device name in lower case letters.
5.3.2
Activating the default IP address
The default IP address 192.168.1.212 can be activated by DIP switch.
Activating the default IP address via the DIP switch
Risk of electric shock when opening the transmitter housing.
‣
Before opening the transmitter housing:
‣
Disconnect the device from the power supply.