omnigrad M TR 44, TR 45

4

Hauser

Response time

Test in water at 0.4 m/s (according to DIN EN 60751; 23 to 33°C step changes)

Insulation

Insulation resistance between terminals and probe sheath

more than 100 MOhm at 25°C

(according to DIN EN 60751, test voltage 250 V)

more than 10 MOhm at 300°C

Self heating

Negligible when E+H iTEMP

®

 transmitters are employed.

Installation

Omnigrad M TR 44 and TR 45 can be mounted on
the wall of pipes or vessels.
The counterparts for the process connections and
the respective gaskets or sealing rings, are generally
not supplied with the sensors, and are considered
to be the customer's responsibility (EHEDG and 3-
A

®

 requirements must be fulfilled). 

The G1" connection is the only exception for which
the sensor with the adaptor to be welded on the
plant can be supplied. 
As a general rule, the sensors should be installed in
such a way that does not adversely affect their
cleanability.
With regard to ATEX-certified components (trans-
mitter, insert), please refer to the specific documen-
tation (see the code at the end of this document).
The immersion length may affect the accuracy of
the sensors. If it is too low, an error might be gen-
erated in the measurement of the temperature, due
to the lower temperatures of the process fluid near
the walls, and to the heat transfer which occurs
through the sensor stem. 
The incidence of such error could be not negligible
if there is a big difference between the process and
the ambient temperature.
To avoid this source of inaccuracy, probes with low
diameter must be employed, and the immersion
length (L) should be, if possible, at least about 80
mm. In small pipes, the axis line of the duct must
be reached, and even slightly exceeded, by the tip
of the probe (see figure 3). 
Insulation on the outer part of the sensor reduces
the effect of the low immersion. Another solution
could be a tilted installation (see figure 2).

Fig. 2:

General installation solutions

In case of two-phase flows, attention should be paid in the choice of the measurement point, which may cause
fluctuations in the detected temperature value. 

Sensor type

Response time

Without thermo-
conductive paste 

With thermo-
conductive paste

TR 44 (

∅ 

6 or 8 mm reduced)

t

50

5 s

-

t

90

13 s

-

TR 45 straight tip

t

50

20 s

10 s

t

90

60 s

30 s

TR 45 tapered tip

t

50

12 s

5 s

t

90

40 s

12 s

TR 45 reduced tip

t

50

7,5 s

3.5 s

t

90

21 s

8 s

Insulation

h<d/2

d

Summary of Contents for omnigrad M TR 44

Page 1: ...nic process connections supplied as standard other on request Customized immersion length Small probe diameter or reduced tip for fast response time TR 44 Tapered or reduced tip and thermoconductive p...

Page 2: ...de the thermowell and spring loaded underneath it so as to improve the heat transfer As in TR 44 the sensing element Pt100 is positioned close to the tip of the probe The TR 45 thermowell is obtained...

Page 3: ...tions Ambient temperature housing without head mounted transmitter metal housings 40 130 C plastic housings 40 85 C Ambient temperature housing with head mounted transmitter 40 85 C Ambient temperatur...

Page 4: ...length may affect the accuracy of the sensors If it is too low an error might be gen erated in the measurement of the temperature due to the lower temperatures of the process fluid near the walls and...

Page 5: ...revices The use of purely threaded Ingold and metal to metal joints is not recommended by some hygienic design standards i e 3 A Standard 74 02 and Document 8 from EHEDG This is the reason why E H Tem...

Page 6: ...division for hygienic applications because it comes in stain less steel and because of its clean design TA20W BUS type is a round grey coloured head made of aluminium with a clip for the cap closure T...

Page 7: ...es for information regarding availability of welding adaptors The Varivent connections must be used with dedicated Tuchenhagen in line components or tank adaptors For Varivent flanges with small nomin...

Page 8: ...some sensor configurations the compliance with the requirements of BN2 can also be assured after the welding and machining operations that is in the finished product The surface roughness Ra of the we...

Page 9: ...omnigrad MTR 44 TR 45 Endress Hauser 9 Fig 9 TR 44 structure and tip designs E L D d R 3 2 20 3 5 3 Reduced...

Page 10: ...nd calibration the inspection test report consists of a declaration of conformity with the essential points of standard DIN EN 60751 The Factory calibration is carried out in the E H EA European Accre...

Page 11: ...DN 10 15 JD SMS DN 25 1 ND Conical metal to metal connection with G1 2 NE Conical metal to metal connection with M12x1 5 YY Special version Neck dimensions E 30 700 mm and d material stainless steel...

Page 12: ...P TMT181 A PCP 2 wire isolated programmable from to C Q TMT181 B PCP ATEX 2 wire isolated programmable from to C R TMT182 A HART 2 wire isolated programmable from to C T TMT182 B HART ATEX 2 wire iso...

Page 13: ...etal connection with G1 2 YY Special version Neck dimensions E 75 250 mm and d material stainless steel 5 82 mm neck length E 15 mm diameter d 6 mm neck length E to specify 15 mm diameter d 9 mm speci...

Page 14: ...from to C P TMT181 A PCP 2 wire isolated programmable from to C Q TMT181 B PCP ATEX 2 wire isolated programmable from to C R TMT182 A HART 2 wire isolated programmable from to C T TMT182 B HART ATEX 2...

Page 15: ...wire isolated programmable from to C L11 TMT182 A HART 2 wire isolated programmable from to C L21 TMT182 B HART ATEX 2 wire isolated programmable from to C L22 TMT182 C HART FM IS 2 wire isolated prog...

Page 16: ...e paste max temperature 200 C mat nr 60007126 _______________ G1 2 metal to metal weld in adapter for flus mounting of ND process connection material SS 316L 1 4435 provided with leakage detectin port...

Page 17: ...nsmitter iTEMP PCP TMT 181 TI 070R 09 en Temperature head transmitter iTEMP HART TMT 182 TI 078R 09 en Temperature head transmitter iTEMP PA TMT 184 TI 079R 09 en RTD insert for temperature sensors Om...

Page 18: ...uarter Endress Hauser GmbH Co KG Instruments International Colmarer Str 6 79576 Weil am Rhein Germany Tel 49 76 21 9 75 02 Fax 49 76 21 9 75 34 5 www endress com info ii endress com TI 244T 02 en_1204...

Reviews: