Micropilot M FMR250 FOUNDATION Fieldbus
Technical data
Hauser
91
10.1.4
Auxiliary energy
Terminals
Cable cross-section: 0.5 to 2.5 mm² (20 to 14 AWG)
Cable entry
• Cable gland M20x1.5 (recommended cable diameter 6 to 10 mm (0.24 to 0.39 in))
• Cable entry G½ or ½NPT
• 7/8" Foundation Fieldbus plug
Supply voltage
9 V to 32 V (Ex)
4)
9 V to 30 V (non Ex)
max. voltage 35 V
Lift-off voltage
9 V
Polarity sensitive
No
FISCO
FNICO compliant
Yes
Basic current
15 mA
In-rush current
≤
15 mA
Error current
0 mA
4)
There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in the appropriate safety instructions (XA).
U
i
17,5 V
I
i
500 mA; with surge arrester 273 mA
P
i
5,5 W; with surge arrester 1,2 W
C
i
5 nF
L
i
0,01 mH