Commissioning
Micropilot M FMR231 with FOUNDATION Fieldbus
64
Hauser
FMR2xx-FF-Methode-in-NIConfig
4.
The method contains the following parameters
3)
:
a. Application parameters (see section 6.4.2)
– PARTANKSHAPE (tank shape)
– PARMEDIUMCONDITION (medium property)
– PARPROCESSCONDITION (process condition)
b. Empty and full calibration (see section 6.4.3)
– PAREMPTYCALIBRATION (empty calibration)
– PARFULlCALIBRATION (full calibration)
c. Interference echo suppression (see section 6.4.4)
– PARCHECKDISTANCE (check distance)
– PARSUPPRESSIONDISTANCE (range of mapping)
– PARSTARTMAPPINGRECORD (start maping)
– PARPRESMAPRANGE (pres. map. dist.)
– PARCUSTTANKMAP (cust. tank map)
5.
Set the operating mode to AUTO in the parameter group MODE_BLK (parameter TARGET).
Otherwise the measured value can not be processed correctly by the connected Analog Input
Block.
6.
If measuring errors occur or if the measuring value seems unreliable, it is advisable to check
the quality of the measurement by the envelope curve display. This can be done in two
different ways:
– by the display and operating module VU331 (see section 6.4.5)
– by an Hauser operating program (see section 6.5.1)
3)
In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display:
- parameter names (e.g. "PARTANKSHAPE")
- label texts (e.g. "tank shape")