Commissioning
Micropilot M FMR231 with FOUNDATION Fieldbus
44
Hauser
• Linearisation is switched to
"linear"
, but the table values are kept. The table can be switched
back on in the
"linearisation" (04)
function group in the
"linearisation" (041)
function.
(FOUNDATION Fieldbus: Sensor Block, Parameter PARLINEARISATION (linearisation))
Performing the reset
"diagnostics" (0A) function group, "reset" (0A3) function; enter "33333"
(FOUNDATION Fieldbus: Diagnostic Block, parameter PARRESET)
6.3.3
Resetting an interference echo suppression (tank map)
It is always adivable to reset the interference echo suppression (tank mapping) when:
• a device with an unknown history is used
• an incorrect suppression was input
Resetting the tank map with the VU331
1.
In the
"extended calibr." (05)
function group select the
"selection" (050)
function.
2.
Select
"extended map."
3.
Go to the
"cust. tank map" (055)
function and select the required option:
–
"reset"
: deletes the existing tank map.
–
"inactive"
: deactivates the tank map but does not delete it. It can be re-activated when
required.
–
"active"
: activates the tank map.
Resetting the tank map with an Hauser operating program
1.
In the function group
"extended calibr."
select the
"cust. tank map" (055)
function.
2.
Select the required option (
"reset"
,
"inactive"
or
"active"
)
Resetting the tank map with a FOUNDATION Fieldbus configuration tool
1.
In the
Sensor Block
select the parameter
PARCUSTTANKMAP (cust tank map)
.
2.
Select the required option (
"reset"
,
"inactive"
or
"active"
).