Micropilot M FMR 240 with PROFIBUS PA
Commissioning
E Hauser
67
display (008)
The
distance
measured from the reference point to the product surface and the
level
calculated with the aid of the empty adjustment are displayed. Check whether the
values correspond to the actual level or the actual distance. The following cases can
occur:
•
Distance correct
−
level correct
→
continue with the next function, "
check
distance
"
(051)
•
Distance correct
−
level incorrect
→
Check "
empty calibr.
"
(005)
•
Distance incorrect
−
level incorrect
→
continue with the next function, "
check
distance
"
(051)
Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured
distance must be compared with the actual distance to the product surface. The
following options are available for selection:
Selection:
•
distance = ok
•
dist. too small
•
dist. too big
•
dist. unknown
•
manual
L00_FMR2xxxxx-14-00-06-en-010
distance = ok
•
mapping is carried out up to the currently measured echo
•
The range to be suppressed is suggested in the "
range of mapping
"
(052)
function
Anyway, it is wise to carry out a mapping even in this case.
⇒
⇒