Summary of Contents for micropilot M FMR 230

Page 1: ...application HART or PROFIBUS PA respectively Foundation Fieldbus protocol High temperatures Suitable for process temperatures up to 200 C 392 F up to 400 C 752 F with high temperature antenna Rod antenna with inactive length Reliable measurement in narrow nozzles with condensation and build up in the nozzle Application The Micropilot M is used for continuous non contact level measurement of liquid...

Page 2: ...c t 2 with c being the speed of light Based on the known empty distance E the level L is calculated L E D Refer to the above figure for the reference point for E The Micropilot is equipped with functions to suppress interference echoes The user can activate these functions They ensure that interference echoes i e from edges and weld seams are not interpreted as level echo Output The Micropilot is ...

Page 3: ...Personal Computer FXA 193 and the operating software ToF Tool The ToF Tool is a graphical operating software for instruments from Endress Hauser that operate based on the time of flight principle radar ultrasonic guided micro impulse It assists with commissioning securing data signal analysis and documentation of the measuring point Remote operation with HART handheld DXR 275 with a Personal Compu...

Page 4: ...integration via Foundation Fieldbus A maximum of 32 transmitters standard EEx em or EEx d can be connected to the bus For protection class EEx ia IIC the max number of transmitters depends on the established rules and standards for intrinsically safe circuits EN 60070 14 proof of intrinsically safety Both on site as well as remote operation are possible The complete measuring system consists of L0...

Page 5: ...el bus system via a Gateway ZA Every HART transmitter via one interface module FXN 672 each Gateways are available for MODBUS FIP PROFIBUS INTERBUS etc Both on site as well as remote operation are possible L00 FMR2xxxx 14 00 06 en 006 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 6: ...ing well in bypass Product class DK εr Examples A 1 4 1 9 non conducting liquids e g liquefied gas 1 B 1 9 4 non conducting liquids e g benzene oil toluene C 4 10 e g concentrated acids organic solvents esters aniline alcohol acetone D 10 conducting liquids e g aqueous solutions dilute acids and alkalis Product class Storage tank scarce draining filling Buffer tank continuous draining filling Tank...

Page 7: ...m 3 ft 2 m 7 ft 3 m 10 ft C DK εr 4 10 6 m 20 ft 10 m 33 ft 15 m 50 ft 20 m 67 ft 3 m 10 ft 5 m 16 ft 7 5 m 25 ft 10 m 33 ft 1 5 m 5 ft 2 m 7 ft 3 m 10 ft 5 m 16 ft D DK εr 10 9 m 30 ft 15 m 50 ft 20 m 67 ft 20 m 67 ft 5 m 16 ft 7 5 m 25 ft 10 m 33 ft 12 5 m 42 ft 2 m 7 ft 3 m 10 ft 5 m 16 ft 7 m 23 ft Product class Stilling well Bypass Wave Guide antenna Measuring range Measuring range Measuring ...

Page 8: ...o guarantee the required accuracy in these cases it is recommended to position the zero point at a distance C above the tank bottom In principle it is possible to measure up to the tip of the antenna However due to considerations regarding corrosion and build up the end of the measuring range should not be chosen any closer than 50 mm 2 to the tip of the antenna The smallest possible measuring ran...

Page 9: ... text display Current output Digital interface Auxiliary energy Electrical connection Terminal compartment Two housings are available Housing F 12 with additionally sealed terminal compartment for standard or EEx ia Housing T 12 with separate terminal compartment for standard EEx e or EEx d L00 FMR2xxxx 04 00 00 en 001 www aotewell com www fa market com info aotewell com AoteWell International inc...

Page 10: ... Hints regarding architecture and grounding of the network can be found in BA 198F projecting hints PROFIBUS PA and the specification for PROFIBUS PA Terminal assignment Foundation Fieldbus The digital communication signal is transmitted to the bus via a 2 wire connection The bus also provides the auxiliary energy Please use 2 wire twisted pair cable with screen Further cable specifications can be...

Page 11: ... max 900 mW Current consumption Communication Current consumption Terminal voltage minimal maximal HART standard 4 mA 16 V 36 V 20 mA 7 5 V 36 V EEx ia 4 mA 16 V 30 V 20 mA 7 5 V 30 V EEx em EEx d 4 mA 16 V 30 V 20 mA 11 V 30 V Fixed current measured value transferred at HART standard 11 mA 10 V 36 V EEx ia 11 mA 10 V 30 V Communication Current consumption HART 3 6 22 mA PROFIBUS PA ca 13 mA Found...

Page 12: ...20 mA FMR 230 1mm 0 1 of measuring range FMR 231 1mm 0 1 of measuring range FMR 240 1mm 0 1 of measuring range Reaction time The reaction time depends on the parameter settings min 1 s In case of fast level changes the instrument needs the reaction time to indicate the new value Influence of ambiente temperature 0 006 10 K referring to max measuring range Type of device to 10 m ex 10 m FMR 230 10 ...

Page 13: ...e Accessories on page 39 Tank installations Avoid any installations 1 like limit switches temperature sensors etc inside the signal beam refer to beam angle Symmetrical installations 2 i e vacuum rings heating coils baffles etc can also interfere with the measurement Optimization options Antenna size the bigger the antenna the smaller the beam angle the less interference echoes Mapping the measure...

Page 14: ... the nozzle otherwise use antenna extension FAR10 Align horn antenna vertically Antenna size 150 mm 6 200 mm 8 250 mm 10 D mm inch 146 5 8 191 7 5 241 9 5 H mm inch 205 8 1 290 11 5 380 15 Installation instructions for enamelled antenna Refer to standard installation Attention Do not hit or chip the enamelled antenna the coating can be damaged Antenna size 150 mm 6 200 mm 8 D mm inch 140 5 5 158 6...

Page 15: ... through plastic walls Medium with dielectric constant εr 10 Maximum level 15 cm 6 below tank ceiling Distance H greater than 100 mm 4 Preferred mounting by means of stand offs for adjustment of the ideal distance H If possible avoid mounting location where condensation or build up might occur In case of outdoor mounting the space between antenna and vessel has to be protected from the elements Op...

Page 16: ...ng the housing can be turned 350 in order to simplify access to the display and the terminal compartment The inactive part of the rod antenna must extend below the nozzle The rod antenna must be aligned vertically Material PPS PTFE Antenna length mm inch 360 14 510 20 360 14 510 20 H mm inch 100 4 250 10 100 4 250 10 L00 FMR231xx 17 00 00 en 001 L00 FMR231xx 17 00 00 en 002 www aotewell com www fa...

Page 17: ...350 in order to simplify access to the display and the terminal compartment The horn antenna should extend below the nozzle If required use version with 100 mm 4 antenna extension see page 25 The horn antenna must be aligned vertically Antenna size 1 40 mm DN50 DN80 DN100 D mm inch 40 1 5 48 1 9 75 3 95 3 7 H mm inch 85 3 4 115 4 5 210 8 3 280 11 L00 FMR240xx 17 00 00 en 001 L00 FMR240xx 17 00 00 ...

Page 18: ... e 180 mm select next larger antenna and adapt it mechanically At any transition i e when using a ball valve or mending pipe segments no gap may be created exceeding 0 1 mm The stilling well must be smooth on the inside average roughness Rz 30 Use extruded or parallel welded stainless steel pipe An extension of the pipe is possible with welded flanges or pipe sleeves Flange and pipe have to be pro...

Page 19: ...M Endress Hauser 19 Examples for the construction of stilling wells L00 FMR2xxxx 17 00 00 en 002 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 20: ... performed through an open ball valve without any problems Recommendations for the bypass pipe Metal no plastic or enamel coating Constant diameter Select horn antenna as big as possible For intermediate sizes i e 95 mm select next larger antenna and adapt it mechanically At any transition i e when using a ball valve or mending pipe segments no gap may be created exceeding 0 1 mm When using a FMR ...

Page 21: ... bypass No alignment is required After mounting the housing can be turned 350 in order to simplify access to the display and the terminal compartment Only suitable for media with low viscosity without the tendency for build up in the Wave Guide antenna L00 FMR240xx 17 00 00 en 003 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 22: ...etermined by the dielectric constant er If the medium tends to cause contamination and deposits cleaning on a regular basis is recommended Care has to be taken not to damage the antenna in the process of a mechanical or hose down cleaning eventually connection for cleaning liquid The material compatibility has to be considered if cleaning agents are used The maximum permitted temperature at the fl...

Page 23: ...s Hauser 23 Mechanical construction Design dimensions Micropilot M FMR 230 L00 FMR230xx 06 00 00 en 001 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 24: ...Micropilot M 24 Endress Hauser Micropilot M FMR 231 L00 FMR231xx 06 00 00 en 001 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 25: ...Micropilot M Endress Hauser 25 Micropilot M FMR 240 L00 FMR240xx 06 00 00 en 001 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 26: ...ass Cable entry M20x1 5 Pg 13 5 gland included NPT G internal thread PROFIBUS PA M12 plug Fieldbus Foundation 7 8 plug Process connection See Ordering information on page 32 38 Seal See Ordering information on page 32 38 Antenna See Ordering information on page 32 38 Micropilot M FMR 230 FMR 231 FMR 240 Weight Approx 6 kg weight of flange Approx 4 kg weight of flange Approx 4 kg weight of flange w...

Page 27: ...s each Display contrast adjustable through key combination Operating elements The operating elements are located inside the housing and are accessible for operation by opening the lid of the housing Function of the keys Symbol on the display continuously on flashes Meaning alarm warning remote communication locked L00 FMR2xxxx 07 00 00 en 001 Key s Meaning or Navigate upwards in the selection list...

Page 28: ...s and functions Within a function application parameters can be read or adjusted The user is guided through a complete configuration procedure Operation with handheld unit DXR 275 All device functions can be adjusted via a menu operation with the handheld unit DXR 275 L00 FMRxxxxx 07 00 00 de 002 L00 FMR2xxxx 07 00 00 yy 002 www aotewell com www fa market com info aotewell com AoteWell Internation...

Page 29: ...nd documentation of the instruments It is compatible with the following operating systems Win95 Win98 WinNT4 0 and Win2000 The ToF Tool supports the following functions Online configuration of transmitters Signal analysis via envelope curve Loading and saving of instrument data Upload Download Documentation of measuring point Menu guided commissioning Signal analysis via envelope curve Connection ...

Page 30: ...r only Foundation Fieldbus The NI FBUS Configurator is an easy to use graphical environment for creating linkages loops and a schedule based on the fieldbus concepts You can use the NI FBUS Configurator to configure a fieldbus network as follows Set block and device tags Set device addresses Create and edit function block control strategies function block applications Configure vendor defined func...

Page 31: ... 231 with PTFE antenna made of 3A FDA listed TFM 1600 Only in combination with food grade process connection Tric lamp dairy coupling and aseptic coupling External standards and guidelines EN 60529 Protection class of housing IP code EN 61010 Safety regulations for electrical devices for measurement control regulation and laboratory use EN 61326 Emissions equipment class B compatibility appendix A...

Page 32: ...HG 6 ATEX II 1 2 G EEx ia IIC T6 WHG 7 ATEX II 1 2 G EEx ia IIC T6 WHG note safety instruction XA for electrostatic charging 8 ATEX II 1 2 G EEx em ia IIC T6 WHG S FM IS Class I Division 1 Group A D T FM XP Class I Division 1 Group A D U CSA IS Class I Division 1 Group A D V CSA XP Class I Division 1 Group A D K TIIS EEx ia IIC T4 Y Special version 20 Antenna size 2 80 mm 3 3 100 mm 4 4 150 mm 6 5...

Page 33: ...lbs ANSI B16 5 SS316Ti A52 10 150 lbs ANSI B16 5 SS316Ti AVT 6 150 lbs ANSI B16 5 enamelled steel A3T 8 150 lbs ANSI B16 5 enamelled steel AV5 6 150 lbs ANSI B16 5 Hastelloy C4 face A35 8 150 lbs ANSI B16 5 Hastelloy C4 face A55 10 150 lbs ANSI B16 5 Hastelloy C4 face KA2 10 K 80 JIS B2210 SS316Ti KH2 10 K 100 JIS B2210 SS316Ti KV2 10 K 150 JIS B2210 SS316Ti KD2 10 K 200 JIS B2210 SS316Ti K52 10 K...

Page 34: ...ic charging F For non hazardous areas WHG 6 ATEX II 1 2 G EEx ia IIC T6 WHG 7 ATEX II 1 2 G EEx ia IIC T6 WHG note safety instruction XA for electrostatic charging 8 ATEX II 1 2 G EEx em ia IIC T6 WHG S FM IS Class I Division 1 Group A D T FM XP Class I Division 1 Group A D U CSA IS Class I Division 1 Group A D V CSA XP Class I Division 1 Group A D K TIIS EEx ia IIC T4 Y Special version FMR 231 Pr...

Page 35: ...S316L PTFE clad AEJ 2 150 lbs ANSI B16 5 SS316L ALJ 3 150 lbs ANSI B16 5 SS316L AMJ 3 300 lbs ANSI B16 5 SS316L APJ 4 150 lbs ANSI B16 5 SS316L AQJ 4 300 lbs ANSI B16 5 SS316L AVJ 6 150 lbs ANSI B16 5 SS316L AEK 2 150 lbs ANSI B16 5 SS316L PTFE clad ALK 3 150 lbs ANSI B16 5 SS316L PTFE clad APK 4 150 lbs ANSI B16 5 SS316L PTFE clad AVK 6 150 lbs ANSI B16 5 SS316L PTFE clad KEJ 10 K 50A JIS B2210 S...

Page 36: ...n 70 Gastight feed through A without gastight feed through C with gastight feed through 80 Additional options A Additional options not selected B 3 1 B material wetted parts SS316Ti Inspection Certificate EN 10204 acc specification 52005759 FMR 231 Complete product designation www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 37: ... Group A D V CSA XP Class I Division 1 Group A D K TIIS EEx ia IIC T4 Y Special version 20 Antenna size 2 40 mm 1 3 50 mm 2 4 80 mm 3 5 100 mm 4 7 mm Wave Guide antenna inside diameter 21 mm 8 inch Wave Guide antenna inside diameter 21 mm 30 Type of antenna sealing temperature Type Sealing Temperature range V Standard Viton FKM 20 C 150 C 4 F 302 F E Standard Viton GLT 40 C 150 C 40 F 302 F K Stan...

Page 38: ... 10 K 80A JIS B2210 SS316L KPJ 10 K 100A JIS B2210 SS316L KWJ 10 K 150A JIS B2210 SS316L YY9 Special version 60 Output and menu based operation A 4 20 mA HART with VU 331 4 line alphanumeric display B 4 20 mA HART C PROFIBUS PA with VU 331 4 line alphanumeric display D PROFIBUS PA E Foundation Fieldbus with VU 331 4 line alphanumeric display F Foundation Fieldbus Y Special version 70 Housing A Alu...

Page 39: ... communication with ToF Tool or Commuwin II via the RS 232C interface Service adapter FXA 193 For communication with ToF Tool via the display connector L00 FMR2xxxx 06 00 00 en 001 10 Material 2 1 4571 4 2 4600 Hastelloy B3 5 2 4610 Hastelloy C4 9 Special material 80 Overall length L1 A 100 mm 4 B 200 mm 8 C 300 mm 12 D 400 mm 16 Y Special length FAR 10 Complete product designation L00 FMRxxxxx 06...

Page 40: ...Instructions for Micropilot M FMR 230 Foundation Fieldbus BA 229F 00 en Operating Instructions for Micropilot M FMR 231 Foundation Fieldbus BA 230F 00 en Operating Instructions for Micropilot M FMR 240 Foundation Fieldbus BA 221F 00 en Description of instrument functions HART PROFIBUS PA Foundation Fieldbus KA 159F 00 a2 Short manual quick reference in housing HART KA 160F 00 a2 Short manual quick...

Page 41: ...2 G XA 106F A Installation Micropilot M FMR 2xx PROFIBUS PA F12 EEx ia IIC T6 PTB 00 ATEX 2117 X Equipment marking II 1 2 G XA 123F A Installation Micropilot M FMR 2xx Foundation Fieldbus F12 EEx ia IIC T6 PTB 00 ATEX 2117 X Equipment marking II 1 2 G XA 124F A Installation Micropilot M FMR 2xx Foundation Fieldbus T12 EEx em ia IIC T6 PTB 00 ATEX 2117 X Equipment marking II 1 2 G XA 125F A Install...

Page 42: ...wing Micropilot M FMR 2xx HART FM XP IS T12 Ex d ia IIC ZD 059F 00 Control drawing Micropilot M FMR 2xx HART CSA IS F12 Ex ia IIC ZD 060F 00 Control drawing Micropilot M FMR 2xx PROFIBUS PA CSA IS F12 Ex ia IIC ZD 061F 00 Control drawing Micropilot M FMR 2xx Foundation Fieldbus CSA IS F12 Ex ia IIC ZD 062F 00 Control drawing Micropilot M FMR 2xx HART CSA XP IS T12 Ex d ia IIC www aotewell com www ...

Page 43: ...Micropilot M Endress Hauser 43 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 44: ...nnover Tel 0511 28372 0 Fax 0511 28372 333 E Mail Vertrieb Hannover de endress com Techn Büro München Stettiner Straße 5 82110 Germering Tel 089 84009 0 Fax 089 84009 133 E Mail Vertrieb Muenchen de endress com Techn Büro Ratingen Eisenhüttenstraße 12 40882 Ratingen Tel 02102 859 0 Fax 02102 859 130 E Mail Vertrieb Ratingen de endress com Endress Hauser Ges m b H Postfach 173 1235 Wien Tel 01 8805...