Wiring
4.1
Quick wiring guide
Wiring in F12/F23 housing
L00-FMP41Cxx-04-00-00-en-003
-
-
"
PA-
PA+
3 4
1 2
PAL
1 2 3 4
7
Made in German
y
D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
HAUSER
t >85°C
TA > 70°C :
D01301-A
if modification
see sep. label
X =
Patents
LEVELFLEX-M
90 … 253 V AC 1VA
10,5 … 32 V DC 1W
16 … 3
V DC 0,8W
Profibus PA
Foundation Fieldbus
LN=
PN=
4 … 20 mA HART
2-wire
1
#
4
5
6
2
3
7
8
EN
DR
ESS
+H
AU
SE
R
HA
USER
Sealed terminal
compartment
Before connection please note the following:
PROFIBUS devices are marked on the nameplate (1). The
voltage is determined by the PROFIBUS standard and the
desired safety concept. (see chapter 4.3).
Connect potential matching line to transmitter
ground terminal
before connecting up the device.
Tighten the locking screw
:
It forms the connection between the antenna and the housing
earth potential.
l
l
l
(7)
(8)
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
On devices supplied with a certificate, the explosion protection
is designed as follows:
Housing F12 - EEx ia:
Power supply must be intrinsically safe.
The electronics and the current output are galvanically
separated from the probe circuit.
l
l
Connect up the Levelflex M as follows:
Unscrew housing cover (2).
Remove any display (3) if fitted.
Remove cover plate from terminal compartment (4).
Pull out terminal module slightly using pulling loop.
Insert cable (5) through gland (6).
Use screened, twisted wire pair.
Only ground screen conductor (7) on sensor side.
Make connection (see pin assignment).
Re-insert terminal module.
Tighten cable gland (6).
Tighten screws on cover plate (4).
Insert display if fitted.
Screw on housing cover (2).
(on dust-Ex torque
40 Nm).
l
l
l
l
l
l
l
l
l
l
l
≈
Caution!
Summary of Contents for Levelflex M FMP43
Page 4: ...Brief overview Levelflex M FMP43 with PROFIBUS PA 4 Endress Hauser...
Page 104: ...Appendix Levelflex M FMP43 with PROFIBUS PA 104 Endress Hauser...
Page 106: ...Levelflex M FMP43 with PROFIBUS PA Index 106 Endress Hauser...
Page 108: ...www endress com worldwide BA358F 00 en 07 07 No 71041163 CCS FM SGML 6 0 ProMoDo 71041163...