iTEMP TMT71
Technical data
Hauser
53
Designation
Standard
Ambient temperature:
Influence (±) per 1 °C (1.8 °F) change
Supply voltage:
Influence (±) per V change
Type L (41)
DIN 43710
-
≤ 0.01 °C
(0.018 °F)
-
Type U (42)
-
0.0 °C (0.0 °F)
-
Type L (43)
GOST
R8.585-2001
-
≤ 0.01 °C
(0.018 °F)
-
Voltage transmitter (mV)
–20 to 100 mV
-
≤ 1.5 µV
0.0015% * MV + 0.003%
≤ 0.8 µV
0.0008% * MV + 0.003%
MV = measured value
LRV = lower range value of the sensor in question
Total measured error of transmitter at current output = √(Measured error digital² +
Measured error D/A²)
Long-term drift, resistance thermometers (RTD) and resistance transmitters
Designation
Standard
Long-term drift (±)
after 1 month
after 6 months
after 1 year
after 3 years
after 5 years
Based on measured value
Pt100 (1)
IEC
60751:2008
≤ 0.039% * (MV - LRV)
+ 0.018% or
0.01 °C (0.02 °F)
≤ 0.061% * (MV - LRV)
+ 0.026% or
0.02 °C (0.04 °F)
≤ 0.007% * (MV -
LRV) + 0.03% or
0.02 °C (0.04 °F)
≤ 0.0093% * (MV -
LRV) + 0.036% or
0.03 °C (0.05 °F)
≤ 0.0102% * (MV -
LRV) + 0.038% or
0.03 °C (0.05 °F)
Pt200 (2)
0.05 °C (0.09 °F)
0.05 °C (0.09 °F)
0.09 °C (0.17 °F)
0.12 °C (0.27 °F)
0.13 °C (0.24 °F)
Pt500 (3)
≤ 0.048% * (MV - LRV)
+ 0.018% or
0.01 °C (0.02 °F)
≤ 0.0075% * (MV -
LRV) + 0.026% or
0.02 °C (0.04 °F)
≤ 0.068% * (MV -
LRV) + 0.03% or
0.03 °C (0.06 °F)
≤ 0.011% * (MV -
LRV) + 0.036% or
0.03 °C (0.05 °F)
≤ 0.0124% * (MV -
LRV) + 0.038% or
0.04 °C (0.07 °F)
Pt1000 (4)
≤ 0.0077% * (MV -
LRV) or
0.02 °C (0.04 °F)
≤ 0.0088% * (MV -
LRV) + 0.03% or
0.02 °C (0.04 °F)
≤ 0.0114% * (MV -
LRV) + 0.036% or
0.03 °C (0.05 °F)
≤ 0.013% * (MV -
LRV) + 0.038% or
0.03 °C (0.05 °F)
Pt100 (5)
JIS
C1604:1984
≤ 0.039% * (MV - LRV)
+ 0.018% or
0.01 °C (0.02 °F)
≤ 0.0061% * (MV -
LRV) + 0.026% or
0.02 °C (0.04 °F)
≤ 0.007% * (MV -
LRV) + 0.03% or
0.02 °C (0.04 °F)
≤ 0.0093% * (MV -
LRV) + 0.036% or
0.03 °C (0.05 °F)
≤ 0.0102% * (MV -
LRV) + 0.038% or
0.03 °C (0.05 °F)
Pt50 (8)
GOST
6651-94
≤ 0.042% * (MV - LRV)
+ 0.018% or
0.02 °C (0.04 °F)
≤ 0.0068% * (MV -
LRV) + 0.026% or
0.04 °C (0.07 °F)
≤ 0.0076% * (MV -
LRV) + 0.03% or
0.04 °C (0.08 °F)
≤ 0.01% * (MV -
LRV) + 0.036% or
0.06 °C (0.11 °F)
≤ 0.011% * (MV -
LRV) + 0.038% or
0.07 °C (0.12 °F)
Pt100 (9)
≤ 0.016% * (MV - LRV)
+ 0.018% or
0.04 °C (0.07 °F)
≤ 0.0061% * (MV -
LRV) + 0.026% or
0.02 °C (0.04 °F)
≤ 0.007% * (MV -
LRV) + 0.03% or
0.02 °C (0.04 °F)
≤ 0.0093% * (MV -
LRV) + 0.036% or
0.03 °C (0.05 °F)
≤ 0.0102% * (MV -
LRV) + 0.038% or
0.03 °C (0.05 °F)
Ni100 (6)
DIN 43760
IPTS-68
0.01 °C (0.02 °F)
0.01 °C (0.02 °F)
0.02 °C (0.04 °F)
0.02 °C (0.04 °F)
0.02 °C (0.04 °F)
Ni120 (7)
Cu50 (10)
OIML R84:
2003 /
GOST
6651-2009
0.02 °C (0.04 °F)
0.03 °C (0.05 °F)
0.04 °C (0.07 °F)
0.05 °C (0.09 °F)
0.05 °C (0.09 °F)
Cu100 (11)
0.01 °C (0.02 °F)
0.02 °C (0.04 °F)
0.02 °C (0.04 °F)
0.03 °C (0.05 °F)
0.04 °C (0.07 °F)
Ni100 (12)
0.01 °C (0.02 °F)
0.02 °C (0.04 °F)
0.02 °C (0.04 °F)
0.02 °C (0.04 °F)
Ni120 (13)
Cu50 (14)
OIML R84:
2003 /
GOST
6651-94
0.02 °C (0.04 °F)
0.03 °C (0.05 °F)
0.04 °C (0.07 °F)
0.05 °C (0.09 °F)
0.05 °C (0.09 °F)
Resistance transmitter