Use in protective systems
Proline Promass 500
38
Hauser
NOTICE
At least 98 % of dangerous, undetected failures are detected using these test sequences
(PTC = 0.98). The influence of systematic errors on the safety function is not fully
covered by the test. Systematic faults can be caused, for example, by medium properties,
operating conditions, build-up or corrosion.
‣
If one of the test criteria from the test sequences described above is not fulfilled, the device
may no longer be used as part of a protective system.
‣
Take measures to reduce systematic errors.
Detailed information on:
• Orientation
• Medium properties
• Operating conditions
Operating Instructions→ 11