Use in protective systems
Proline Promass 500
22
Hauser
to lock the device software to ensure that parameters cannot be changed. Non-safety-related
parameters remain unchanged.
NOTICE
Once the SIL device has been locked, the process-related parameters are write protected,
and thereby locked, for security reasons.
It is still possible to read the parameters. When SIL locking is enabled, restrictions apply on all
communication options, such as the service interface, HART protocol and WirelessHART
protocol, local display and WLAN.
‣
Follow the specified locking sequence.
1. Ensure preconditions are met.
* ... unit
user-defined unit
≠
Partial filled
pipe detection
Assign
process variable
Current output 1
Setup
Assign
current output 1
Partial filled
pipe detection
Current span
Failure mode
Assign
process variable
= Mass flow* or
= Vol. flow*
or
= Density*
= 4...20 mA
or
=
or
= 4...20 mA US
4...20 mA NAMUR
= Min. or
= Max.
= Off
= Density
or
Select medium
Pressure
compensation
= Off
= Fixed value
or
= Off
or
=
=
Mass flow or
Vol. flow
A0015325-EN
2. In the
Setup
menu →
Advanced setup
submenu, select the
SIL confirmation
wizard.
3. Select
Set write protection
parameter.
4. Enter the SIL locking code
7452
.
The device first checks the preconditions listed under item 1.