Deltabar S
10
Hauser
Output
Output signal
• 4...20 mA with superimposed digital communication protocol HART 5.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0)
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
• Digital communication signal FOUNDATION Fieldbus
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
Signal range –
4...20 mA HART
3.8 mA to 20.5 mA
Signal on alarm
As per NAMUR NE 43
• 4...20 mA HART
Options:
– Max. alarm*: can be set from 21...23 mA
– Keep measured value: last measured value is kept
– Min. alarm: 3.6 mA
* Factory setting: 22 mA
• PROFIBUS PA: can be set in the Analog Input block,
options: Last Valid Out Value, Fsafe Value (factory setting), Status bad
• FOUNDATION Fieldbus: can be set in the Analog Input Block,
options: Last Good Value, Fail Safe Value (factory setting), Wrong Value
Load – 4...20 mA HART
P01-xMD7xxxx-05-xx-xx-xx-000
Load diagram, observe the position of the jumper and the explosion protection (
17, section "Taking 4...20 mA test
signal".)
1
Jumper for 4...20 mA test signal inserted in "Non-test" position
2
Jumper for 4...20 mA test signal inserted in "Test" position
3
Supply voltage 10.5 (11.5)...30 V DC for 1/2 D, 1 GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia
4
Supply voltage 10.5 (11.5)...45 V DC for device for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA, FM
XP, FM DIP, FM NI, CSA XP, CSA Dust-Ex, NEPSI Ex d
R
Lmax
Maximum load resistance
U
Supply voltage
Note!
When operating via a handheld terminal or via PC with an operating program, a minimum communication
resistance of 250
must exist within the loop.
Resolution
• Current output: 1
A
• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
U – 10.5 V
R
Lmax
23 mA
≤
30
20
10.5
U
[V]
40 45
1282
1500
847
413
[ ]
Ω
R
Lmax
30
20
11.5
U
[V]
40 45
1239
1456
804
369
[ ]
Ω
R
Lmax
Test
Test
➀
➁
U – 11.5 V
R
Lmax
23 mA
≤
➂
➃
➂
➃