Deltabar S
Hauser
17
Devices with 7/8" plug
P01-xxx7xxxx-04-xx-xx-xx-003
Left: electrical connection for devices with 7/8" plug
Right: view of the plug at the device
Kabel gland
Terminals
for wire cross-sections of 0.5 to 2.5 mm
2
Taking 4...20 mA test signal
A 4...20 mA signal may be measured via the positive and test terminal without interrupting the measurement.
The minimum supply voltage of the device can be reduced by simply changing the position of the jumper. As
a result, operation is also possible with lower voltage sources. Observe the position of the jumper in accordance
with the following table.
–
+
7/8”
–
+
+ –
Approval
Typ
Clamping range
Standard, II1/2G Exia, IS
Plastic M20x1.5
5...10 mm
ATEX II1/2D, II1/3D,
II1/2GD Exia, II1GD Exia
II3G Ex nA
Metal M20x1.5 (Ex e)
7...10.5 mm
Jumper position for test signal
Description
– Taking 4...20 mA test signal via plus and test terminal:
possible. (Thus, the output current can be measured without
interruption via the diode.)
– Delivery status
– minimum supply voltage: 11.5 V DC
– Taking 4...20 mA test signal via plus and test terminal:
not possible.
– minimum supply voltage: 10.5 V DC
Test
Test
Test