7 Trouble-Shooting
ControlCare Field Controller: Commissioning and Configuration
56
Hauser
5 Press the
Hold
button to interrupt the firmware that is being executed in the module
–
A confirmation window appears, press
Yes
to continue
–
Any application running on the Field Controller will be stopped at this point
6 Check that the HOLD LED on the Controller module is lit, then press
Connect
to continue
with the procedure.
7 Reselect the desired Controller module
–
Note the current firmware version installed in the Field Controller
8 Click on the browse button "
..."
–
The computer automatically locates all firmware versions and displays them in a dialog box
–
SFC1xx-VXX.YY.ZZ-A
SFC1xx is the Field Controller designation
VXX.YY.ZZ is the Firmware Version number
–
Firmware with the same primary version index ("V
XX."
) as the old firmware will run in the
Field Controller
9 Select the latest firmware version, then press
Open
–
– The program returns to the overview window