5 Configuring the Field Controller
ControlCare Field Controller: Commissioning and Configuration
34
Hauser
5.3.3
Analog Input block
The Analog Input block is fully configurable and provides characterization for the incoming signal.
The
OUT
value has the range and units configured in the
OUT_SCALE
parameter.
Fig. 5-2 Schematic diagram of Analog Input block
Procedure
1 In the fieldbus view, right click on the Analog Input block
Device Tag-AI-n
and select
Off
Line Characterization
. The Characterization dialog opens.
– Press the
ALL
button in the toolbar to display all parameters
2 Expand the
MODE_BLK
node and set the Target Mode to Auto
–
Select the
Target
node then click the
Edit
button
–
Select
Auto
from the drop-down menu, click
End Edit
to confirm the selection
–
Click
Close
to leave the dialog.
3 Set
CHANNEL
to the input connected to the block as defiined in Section 5.3.1
–
Select
CHANNEL
, then click the
Edit
button
–
Enter the CHANNEL value (Rack+Slot+Group+Point)
–
Click on
End Edit
4 Set
L_TYPE
to "Indirect" or "Indirect Sq Root" (for
∆
p flow analog input)
–
Select
L_TYPE
, click the
Edit
button, select parameter , then click on
End Edit
5 Expand
XD_SCALE
and set the parameters according to the signal from the input point.
–
EU_100 is the upper range limit of the input signal, e.g. 20
–
EU_0 is the lower range limit of the input signal, e.g. 4
–
UNIT_INDEX is the unit of the input signal, e.g. mA
–
DECIMAL is the number of figures behind the decimal point
In each case click the
Edit
button, enter or select parameter , then click on
End Edit
For the SFC445 Temperature module, the ranges and units are listed overleaf.
6 Expand
OUT_SCALE
and set the parameters according to the signal to be output.
–
EU_100 is the upper range limit of the output signal, e.g. 100
–
EU_0 is the lower range limit of the output signal, e.g. 0
–
UNIT_INDEX is the unit of the output signal, e.g. %
–
DECIMAL is the number of figures behind the decimal point
In each case click the
Edit
button, enter or select parameter , then click on
End Edit
7 For flow measurements a low-flow cut-off limit can be set as follows:
–
Select the
IO_OPTS
parameter and click on
Edit
–
Select the
Low Cut-Off
option and click
End Edit
–
Select the
CUT_OFF
parameter, click on
Edit
, enter the limit in OUT_SCALE units
–
Click on
End Edit
.
CHANNEL
(RRSGP)
SIMULATE
OUT
XD_SCALE
OUT_SCALE
XD_SCALE
FIELD_VAL(X)
SIMULATE
OUT_SCALE
LOW_CUT
PV_FTIME
ALARMS
DIRECT
INDIRECT
IND_SQRT
L_TYPE
IO_OPTS
PV
MANUAL
AUTO
From modules
SFC444
SFC445
SFC457