5 Configuring the Field Controller
ControlCare Field Controller: Commissioning and Configuration
38
Hauser
5.3.6
Multiple Analog Input block
The Multiple Analog Input block scales up to eight electrical input signals of 4 mA to 20 mA or
1 mV to 5 mV to
OUT_x
values of 0% to 100%. The block can be used together with the SFC444
and SFC457 analog input modules. If other input signals are used with these modules, Analog Input
blocks must be used.
Fig. 5-5 Schematic diagram of Multiple Analog Input block
Procedure
1 In the fieldbus view, right click on the Multiple Analog Input block
Device Tag-MAI-n
and
select
Off Line Characterization
. The Characterization dialog opens.
– Press the
ALL
button in the toolbar to display all parameters
2 Expand the
MODE_BLK
node and set the Target Mode to Auto
–
Select the
Target
node then click the
Edit
button
–
Select
Auto
from the drop-down menu, click
End Edit
to confirm the selection
–
Click
Close
to leave the dialog.
3 Set
CHANNEL
to the input connected to the block as defiined in Section 5.3.1
–
Select
CHANNEL
, then click the
Edit
button
–
Enter the CHANNEL value (Rack+Slot+Group+
9
)
–
Click on
End Edit
Properties
The input channels of the SFC444 and SFC457 can be configured individually by jumpers on the
printed circuit board to accept current or voltage signals, default setting current, see Chapter 3.5.1
of operating instructions BA021S/04/en, Field Controller: Hardware Installation. The OUT value
is proportional to the electrical signal over the range 0 mA to 40 mA and 0 V to 10 V. The MAI
block converts the input as shown in Table 5-2.
Tab. 5-2: OUT value as a function of input signal for SFC444 and SFC457 modules
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
MODE
CHANNEL
INPUT
SNAPSHOT OF
HC TRANSDUCER
BLOCK
OUTPUTS
From modules
SFC444
SFC457
I/O points
AI 0 to AI 7
together
RRSG
9
Value
Current
Voltage
Input value
OUT value
OUT status
Input value
OUT value
OUT status
Underrange limit
0 mA
-25%
GOOD
0 V
-25%
GOOD
Lower range limit
4 mA
0 %
GOOD
1 V
0 %
GOOD
Upper range limit
20 mA
100%
GOOD
5 V
100%
GOOD
Overrange limit
40 mA
225%
GOOD
10 V
225%
GOOD
Out of range
>40 mA
BAD
BAD
>10 V
BAD
BAD