6 Going On-line
ControlCare Field Controller: Commissioning and Configuration
50
Hauser
15 Now return to FC Tools and click on
Run
to start the execution of the Field Controller
firmware again
16 Check that the HOLD LED on the Field Controller has extinguished, then press
Close
.
–
If the HOLD LED does not extinguish, there is a communication problem:
Type PING the new IP address in the DOS command window and check whether the Field
Controller is found. If there is a reply, replace the Ethernet cable by a cross-cable and try
Step 10 again.
17 The selected Controller module has now been connected. Now repeat Steps 1 to 16 for all
other Controller modules.
18 When IP addresses have been assigned to all Field Controllers, reset your computer’s address to
the original values.