Cerabar S PMP71
Appendix
Hauser
37
8.2.1
Pressure device parameter configuration form
Operation via:
Handheld terminal
FieldCare/DeviceCare
On site
Device designation:
Serial number:
Measuring
point:
Upper range limit (URL sensor):
Parameter name
Direct
access
Menu path:
Expert
Factory setting
Permitted
settings
Set
point
Actual
value
Tested
Digit set
840
→ Display
012345
67890.-
Calib. offset
319
→ Position
adjustment
0.0
Measuring mode
389
Pressure
Pressure
Set LRV
245
→ Quick Setup /
Basic Setup
0.0 or as per order
Set URV
246
URL sensor or as per order
Damping value
247
2 s
0 to 999 s
Press. eng. unit
060
→ Basic setup
mbar/bar
or as per order
All
except "user unit"
Current charact.
695
→ Output
Linear
Linear
Output fail mode
388
Max. alarm
Max. alarm
Min. alarm
Alt. curr. output
597
Normal
Normal
Set max. alarm
342
22 mA
21 to 23 mA
Set min. current
343
3.8 mA
3.8 mA or 4 mA
Simulation
413
→ Simulation
None
None
Ack. alarm mode
401
→ Messages
Off
Off/On
Error No. Select alarm
type
The following messages
must be set to "Alarm":
595/600
115 Sensor over pressure
Warning
Alarm o. warning
120 Sensor low pressure
Warning
Alarm o. warning
715 Sensor over
temperature
Warning
Alarm o. warning
717 Transmitter over
temp.
Warning
Alarm o. warning
718 Transmitter under
temp.
Warning
Alarm o. warning
720 Sensor under
temperature
Warning
Alarm o. warning
726 Sens. temp. error
overrange
Warning/alarm
Alarm
727 Sens. pres. error
overrange
Warning
Alarm o. warning
620 Current output out
of range
Warning
Alarm o. warning
Alarm delay
336
0.0 s
0.0 s
Alarm display time
480
0.0 s
0.0 s