In some cases, (e.g. failure of power supply, a cable open circuit and faults in the
current output itself, where the error current ≥ 21 mA cannot be reached), output
currents ≤ 3.6 mA occur irrespective of the configured failure current. In some other
cases, (e.g. cabling short circuit), output currents ≥ 21.0 mA occur irrespective of the
configured failure current.
‣
For alarm monitoring, the downstream logic unit must be able to recognize failure
currents of the upper level for signal on alarm (≥ 21 mA) and the lower level for signal
on alarm (≤ 3.6 mA).
5.3
Alarm and warning messages
5.3.1
List of alarm and warning messages
Additional information is provided by the alarm and warning messages in the form of
error codes and associated plain text messages.
Parameter
Description
Factory setting
Parameterization method with increased security during parameter
entry
FW 02.20 FW ≥ 02.30.zz Permitted SIL setting
FW ≤ 02.20
FW ≥ 02.30.zz
115
Sensor over pressure
Warning
Warning
Warning or alarm
Alarm
As per client setting
(default: warning)
120
Sensor low pressure
Warning
Warning
Warning or alarm
Alarm
620
Current output out of range Warning
Warning
Warning or alarm
Alarm
715
Sensor over temperature
Warning
Warning
Warning or alarm
Alarm
720
Sensor under temperature
Warning
Warning
Warning or alarm
Alarm
717
Transmitter over temp.
Warning
Warning
Warning or alarm
Alarm
718
Transmitter under temp.
Warning
Warning
Warning or alarm
Alarm
726
Sens. temp. error overrange Warning
Alarm
Alarm
Alarm
Alarm
727
Sens. pres. error
overrange
Warning
Warning
Warning or alarm
Alarm
As per client setting
(default: warning)
Alarm current Output fail mode
MAX
MAX
MIN. or MAX
MAX
As per client setting
(default: MAX.)
1)
Settings are automatically changed from warning to alarm via the parameterization method
2)
The setting influences the parameters for functional safety
L
WARNING
In the case of devices with firmware version ≤ 02.20.04, certain messages in the
SAFETY CONFIRM. menu (increased security during parameter entry) are
automatically set from warning to alarm.
Do not use the SAFETY CONFIRM. sequence if the pressure in the applications is outside
the set current or measuring range.
‣
Standard device configuration and software/hardware locking is recommended in such
applications.