CE 4
Maintenance and cleaning
Hauser
21
Sensor rinse:
Fig. 15:
Time cycles for automatic sensor rinse using "Chemo-Clean"
7.3.4
Cleaning system control
The mini-controller LOGO from Siemens takes on the following functions:
•
Automatic clean water rinsing system (
→
Chap. 7.3.2) and
•
automatic cleaning system "Chemo-Clean" (
→
Chap. 7.3.3)
Fig. 16:
SIEMENS mini-controller "LOGO! 12/24RC"
Pos. A: Operating keys "Up" "Down", "Left", "Right"
Pos. B: Operating keys "ESC", "OK"
The controller default programme is dependent on the cleaning system ordered. This
means that the programme can be immediately started by using the "
Cleaning ON/
OFF
" switch (found in the swing frame), and the system will then operate using the
factory defaul set-up times.
on
off
A
E / F / G
I
K
G
F
E
on
Pos.
Function
Set up address
Time interval
Factory default
A
Start hose rinse
B01
(0...99h)
24h
B
Hose rinse time
B02
(0...99s)
45s
C
Pump rinse time
B03
(0...99s)
30s
D
Start sensor rinse
B04
(0...99h)
18h
E
Post rinse
B05
(0...99s)
10s
F
Clean (detergent)
B06
(0...99s)
30s
G
Pre-rinse
B07
(0...99s)
10s
H
Hold time after suction hose rinse
B08
(0...99s)
20s
I
Pump status
K
Hold (transmitter)
A
B
12/24RC