Fastlane
®
Pro Swim Unit Installation
Hydraulic Power Unit
Pool Equipment
Bonding Test Wire
Multi Meter
Test
Lead
Tes
t L
ea
d
Bonding Connection
Ω
Metal Reinforcement /
Pool Bonding Grid
1
2
3A
Multi Meter
Ω
3B
Bonding Test Wire Te
st
Lea
d
Te
st
Le
ad
Testing Fastlane Bonding
Bonding Connection
1) Attach stainless steel "Bonding Test Wire" to the bonding lug located on the hydraulic power unit.
2) Run the test wire across the pool deck to the Fastlane bonding connection. For Wall Mount units,
the connection will be at the threaded mounting rod (as shown). For Deck Mount units it will be
at the hose cover tray.
3A) Set the multimeter to resistance (continuity
Ω
). Place one test lead on the test wire and the other
test lead on the Fastlane bonding connection point (where the stainless steel wire that exits the
top of the Fastlane is attached). (Refer to Test Results Below)
3B) Run test wire to the existing pool equipment (pump, heater, ladder, etc) to test continuity bewteen
the hydraulic power unit and pool equipment. Place one test lead on the test wire and the other
test lead at the bonding connection at the pool equipment. (Refer to Test Results Below)
Test Results:
Continuity = Properly Bonded Unit
No Continuity / Open Line = Improper Bonding OR Disconnected Bonding Circuit. This requires
repair prior to using the FastLane.
Fig. 13.3
45