Measured value
INPUT REGISTERS
0000d
0x0000
word
Read Only
–
0001d
0x0001
word
0002d
0x0002
word
–
–
Minimum measured value
Maximum measured value
Read Only
Read Only
Decimal
Hex
OUT Control output condition. (0=OFF; 1=ON).
DISCRATE INPUTS
0000d
0x0000
bit
Read Only
–
0001d
0x0001
bit
–
Alarm control output condition. (0=OFF; 1=ON).
Read Only
Coil
Addresses
Decimal
Hex
Indicator configuration oFF=
pr.C5
,
ON=
Pr.Un
COILS
0000d
0x0000
bit
R W
d5p.C
0001d
0x0001
bit
Cal.t
Calibration type
oFF=
5.Inp
,
ON=
U.Inp
R W
Holding Register
Addresses
Decimal
Hex
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Input type selection.
0=
0-20
;1=
4-20
;2=
0-1
;3=
0-10
Output set value.
*
Holding and Input Register parameters, which in integer type is defined as signed integer. Timing parameters are defined as seconds.
(For example, 01:15 is defined as 75 seconds).
HOLDING REGISTERS
MODBUS ADDRESS MAP
0000d
0x0000
word
R W
i.tyP
0001d
0x0001
word
0002d
0x0002
word
0003d
0x0003
word
0004d
0x0004
word
0005d
0x0005
word
0006d
0x0006
word
0007d
0x0007
word
0008d
0x0008
word
0009d
0x0009
word
0010d
0x000A
word
0011d
0x000B
word
0012d
0x000C
word
0013d
0x000D
word
0014d
0x000E
word
0015d
0x000F
word
0016d
0x0010
word
0017d
0x0011
word
0018d
0x0012
word
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
RAtE
hold
d.pnt
l.5Cl
H.5Cl
o.5Et
o.Hy5
o.5ta
o.pon
o.ton
o.tof
a.5Et
a.HY5
A.typ
A.5ta
a.pon
a.ton
a.tof
Measurement ranges. 0=
Fa5t
;1=
5.lo1
;2=
5.lo2
;3=
5.lo3
Indicator locking parameter. 0=
nonE
;1=
lo
;2=
HI
Decimal point. 0=x;1=x.x;2=x.xx;3=x.xxx
Scale lower value.
Scale upper value.
Output hysteresis value.
Output condition. (0=
OFF
,1=
Lo
, 2=
H1
)
Alarm set value.
Alarm hysteresis value.
Alarm type. 0=
IndE
;1=
dE
;2=
band
Alarm condition. 0=
OFF
, 1=
Lo
;1=
H1
;2=
b1.H1;
3=
bo.H1
Required relay-on delay time in order to set output to active state after power-up.
Output relay-on delay time.
Output relay-off delay time.
Required relay-on delay time in order to set alarm output to active state after power-up.
Alarm output relay-on delay time.
Alarm output relay-off delay time.
Holding Register
Addresses
Decimal
Hex
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Holding Register
Addresses
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah.
Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-
TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
Barbaros Cad. No:
18
EI2041-EN-01-
180411
5
/5
ENDA
TM
* MODBUS CONNECTION DIAGRAM
1
2
0
O
h
m
120 Ohm
Master
Slave - 1
Up to 127 slave devices
can be controlled.
Slave - 2
Slave - 127
A
B
A
B
A
B
A
B
Termination should be accomplished by
attaching 120 Ohm resistors to the start
and at the end of the communication line.