background image

Measured value

     INPUT REGISTERS

0000d

0x0000

word

Read Only

0001d

0x0001

word

0002d

0x0002

word

Minimum measured value

Maximum measured value

Read Only

Read Only

Decimal

Hex

OUT Control output condition. (0=OFF; 1=ON).

     DISCRATE INPUTS

0000d

0x0000

bit

Read Only

0001d

0x0001

bit

Alarm control output condition. (0=OFF; 1=ON).

Read Only

Coil 

Addresses

Decimal

Hex

Indicator configuration  oFF=

pr.C5

,

 ON=

Pr.Un

     COILS

0000d

0x0000

bit

R W

d5p.C

0001d

0x0001

bit

Cal.t

Calibration type 

oFF=

5.Inp

,

 ON=

U.Inp

R W

Holding Register

Addresses

Decimal

Hex

Data

Type

Data Content

Parameter

Name

Read / Write

Permission

Input type selection. 

 

0=

0-20

;1=

4-20

;2=

0-1

;3=

0-10

Output set value.

*

 Holding and Input Register parameters, which in integer type is defined as signed integer. Timing parameters are defined as seconds.

(For example, 01:15 is defined as 75 seconds).

     HOLDING REGISTERS

MODBUS ADDRESS MAP

0000d

0x0000

word

R W

i.tyP

0001d

0x0001

word

0002d

0x0002

word

0003d

0x0003

word

0004d

0x0004

word

0005d

0x0005

word

0006d

0x0006

word

0007d

0x0007

word

0008d

0x0008

word

0009d

0x0009

word

0010d

0x000A

word

0011d

0x000B

word

0012d

0x000C

word

0013d

0x000D

word

0014d

0x000E

word

0015d

0x000F

word

0016d

0x0010

word

0017d

0x0011

word

0018d

0x0012

word

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

R W

RAtE

hold

d.pnt

l.5Cl

H.5Cl

o.5Et

o.Hy5

o.5ta

o.pon

o.ton

o.tof

a.5Et

a.HY5

A.typ

A.5ta

a.pon

a.ton

a.tof

Measurement ranges. 0=

Fa5t

;1=

5.lo1

;2=

5.lo2

;3=

5.lo3

 

Indicator locking parameter. 0=

nonE

;1=

lo

;2=

HI

 

Decimal point. 0=x;1=x.x;2=x.xx;3=x.xxx 

Scale lower value. 

Scale upper value.

Output hysteresis value.

Output condition. (0=

OFF

,1=

Lo

, 2=

H1

)

Alarm set value.

Alarm hysteresis value.

Alarm type. 0=

IndE

;1=

dE

;2=

band

Alarm condition. 0=

OFF

, 1=

Lo

;1=

H1

;2=

b1.H1;

3=

bo.H1

Required relay-on delay time in order to set output to active state after power-up.

Output relay-on delay time.

Output relay-off delay time.

Required relay-on delay time in order to set alarm output to active state after power-up.

Alarm output relay-on delay time.

Alarm output relay-off delay time.

Holding Register

Addresses

Decimal

Hex

Data

Type

Data Content

Parameter

Name

Read / Write

Permission

Holding Register

Addresses

Data

Type

Data Content

Parameter

Name

Read / Write

Permission

Data

Type

Data Content

Parameter

Name

Read / Write

Permission

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 

Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-

TURKEY

Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:

18

      EI2041-EN-01-

180411

 

5

/5

ENDA

TM

* MODBUS CONNECTION DIAGRAM

1

2

0

 O

h

m

120 Ohm

Master

Slave - 1

Up to 127 slave devices 
can be controlled.

Slave - 2

Slave - 127

A

B

A

B

A

B

A

B

Termination  should  be  accomplished  by 
attaching  120  Ohm  resistors  to  the  start 
and at the end of the communication line.

*  Applies to devices with Modbus function.