background image

RE5

I.typ

baUd

C.Fos

C.Fos

Baud

Hidden Menu

Parameter Transfer Between Menus

PROGRAMMING DEVICE

Changing Parameters

240

1000

571

1453

1000

571

rE5

1000

571

In "Running Mode", if          key pressed for 2 seconds, maximum and minimum measurement values become

equal to the measured value at current time and the                 message appears on display.

SET

&

SET

unl

Locking and Unlocking

1000

571

Loc

Keys are locked.

Keys are unlocked.

SET

SET

Displaying the Measurement Unit

Measurement

Value

bAr

1000

571

In “Running Mode”, if                  keys are pressed together for 3 seconds, measurement unit appears. See 

Unit

 parameter for programming.

&

 Setting Up User Calibration Values

&

SET

SET

Programming Mode

I.typ

Factory Defaults

d.Par

Viewing the Revision

r

.

001

&

SET

&

SET

SET

SET

Running Mode Error Messages

   L.inp.

    

   H.inp.

Setting Up 

Parameters

Measurement Unit (

Unit

  Err.1

    

   Err.2

  C.Err

    

Displaying the Minimum Measurement Unit

Measurement

Value

In “Running Mode”, if         key is pressed for 3 seconds,
minimum measurement value appears. 

Measurement

Value

In “Running Mode”, if         key is pressed for 3 seconds, 
maximum measurement value appears. 

Displaying the Maximum Measurement Unit

Resetting Maximum and Minimum Measurement Values

Measurement

Value

Measurement

Value

If                keys are pressed together for 2 seconds, 

Loc

 message appears and keys are 

locked. For unlocking,                keys are pressed together for 2 seconds, 

unL

 message 

appears and keys are unlocked. If one of the keys is pressed while the device locked, 

Loc

 

message appears on display.

ERROR MESSAGES & DESCRIPTIONS

Error conditions and descriptions are listed below.

*

 If voltage or current is difference and lower than half of full scale between 

H.inP

 and 

L.inP

 voltage or current. 

*

 If excessive high-low input current or voltage is applied.

*

 If an error occurs during 

L.inP

 calibration, 

Err1

 message appears on display. 

*

 If an error occurs during 

H.inP

 calibration, 

Err2

 and 

C.Err

 message appears on display.

*

 If user calibration 

is not applied

 before and an error occurs during calibration process, device runs according to standard calibration values.

*

 If user calibration 

is applied

 before and an error occurs during calibration process, device runs according to previous user calibration values.

Input voltage or input 

current below zero.

Input voltage higher then 15V

or

input current higher than 25mA.

L.INP

  calibration
error

Calibration failed

H.INP

 calibration

error

If                         keys are pressed together for 2 seconds, 

Pi

 message appears and user menu entered. Then in user menu, first parameter's is displayed.

When a parameter selected, if        key is pressed selected parameter value appears and displayed parameter can be changed by              keys. If no 
operation is performed for 3 seconds after the parameter value is being displayed or        key is pressed, parameter name will be shown again. While 
parameter name displayed,              keys are pressed together, returned to "Running Mode" without waiting period. 

SET

SET

No calibration required if the standard inputs (0-20mA, 4-20mA, 0-1V and 0-10V) are used.  

Cal.t

  Parameter should be set as  

U.Inp

   if no standard input used.

In user menu, if           key is pressed for 7 seconds,               message  appears on display and calibration menu is entered. 

L.INP

Voltage or current which are corresponds to  

L5Cl

  parameter is applied to device input and         key is pressed.  If operation is success,              message appears on 

display and proceeding to the next step.

5ucc

SET

In this step, while              message displayed, voltage or current which are corresponds to  

L5Cl

  parameter is applied to device input and         key is pressed.  If operation is 

success,              then             message appears on display, calibration process is completed and the device will start running according to the new calibration values.

H.inp

5ucc

C.End

SET

If        key is 

for 7 seconds  

P2

  message appears on the display and hidden menu is entered. Selected 

parameter values can be displayed with        key and canged with               keys. Accessing to the parameters and 
storing functions are as in the user menu. All parameters can be accessed from this menu.

pressed 

If               keys are pressed together for 2 seconds, parameter transferred to user menu. In this way up to 12 

parameters can be transferred to the user menu. 

In user menu, if               keys are pressed together for 2 seconds, parameter is removed from user menu. When a 

parameter is displayed in the user menu, mA LED lights up in the hidden menu.

SET

SET

SET

If pressed        key in 

Unit

 parameter, related digit blinks on display. For desired number, letter or symbol is adjusted by pressing the         key for related digit. For 

setting up other digits         key is pressed.   When parameter setting process is completed, by pressing         key or no key is pressed for 3 seconds without pressing any 

key, parameters can be saved.

         Key is held down while the device is powered up,             

message will see and restore the factory parameters

In “Running Mode”, if                                  keys are  pressed together for 3 seconds,              

                 revision information appears on display. 

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 

Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-

TURKEY

Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:

18

      EI2041-EN-01-

180411

 

3

/5

ENDA