background image

SET

mA  LED     : 

If input type is selected as 0-20mA or 4-20mA, 

mA LED

 lights up.

                In "Running Mode", indicates output set value.
                In “Programming Mode”, indicates the selected parameter value.

V  LED        :

 If input type is selected as 0-1V or 0-10V, 

V LED

 lights up.

  ALR  LED   : 

If alarm output is active, 

ALR LED

 lights up. During delay time, LED flashes. 

OUT  LED   : 

If “OUT” is active, 

OUT LED

 lights up. During delay time, LED flashes.

FRONT PANEL

ENDA EI2041

 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding 

must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. 
The device must be protected against inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not 
exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These 
cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a 
qualified staff and must be according to the relevant locally applicable regulations. 

Panel cut-out

Note :
1)

 While panel mounting, additional distance required

for connection cables should be considered.

2)

 Panel thickness should be maximum 7mm.

3)

 If there is no 60mm free space at back side of the 

device, it would be difficult to remove it from the panel.

71,5mm

2

9

,5

m

m

To removing the mounting clamps :

-

 Push the flush-mounting

clamps in direction 

1

 

-

 Pull out the clamps in direction 

2

.

Depth

Rubber packing

2

71mm

5mm

Panel

3

5

m

m

77mm

DIMENSIONS

CONNECTION DIAGRAM

EI2041-230
PROGRAMMABLE INDICATOR

Made in Turkey

1

2

3

4

5

6

7

8

9

10

ENDA

 

INDUSTRIAL ELECTRONICS

SN: XXXXXXXXX

230V AC
 50/60Hz

11 12

8 680407 721603

INPUT

+

GND

11 12 13

           A

           B

         COM

EI2041-230-2R-05-RS
PROGRAMMABLE INDICATOR

Made in Turkey

1

2

3

4

5

6

7

8

9

10

ENDA

 

INDUSTRIAL ELECTRONICS

SN: XXXXXXXXX

230V AC
 50/60Hz

8 680407 722204

INPUT

+

GND

OUT

250V 8A~

AUX SUPPLY

+

GND

ALARM

250V 8A~

Flush

mounting

clamp

1

IN

P

U

T

+

 

G

N

D

1

2

3

4

5

6

7

8

9

10

11

12

EN

DA

 

IN

DU

ST

RIA

L E

LE

CT

RO

NIC

S

2

3

0

V

 A

C

 +

1

0

%

 - 

2

0

%

5

0

/6

0

H

  7

V

A

SN

: X

XX

XX

XX

XX

Ma

de

 In

 T

urk

ey

Flush

mounting

clamp

1

2

2

86

804

07

721

603

EI2

04

1-2

30

PR

OG

RA

MM

AB

LE

 IN

DIC

AT

OR

In "Running Mode", indicates the maximum measured value.
Used for incrementing values in "Programming Mode".

In "Running Mode", indicates the minimum measured value.
Used for decrementing values in "Programming Mode".

Flush

mounting

clamp

1)

 Mains supply cords shall meet the requirements of  IEC 60227 or IEC 60245. 

2)

 In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it

   should  be easily accessible by the operator.

Note :

 2

1

184-253V AC 
50/60Hz 7VA

230V AC 
Supply

Switch

Cable size: 1,5mm²

Fuse

F 100 mA 

250V AC

Neutral

Line

SUPPLY :

NOTE :

Fuse should
be connected

Holding screw

 0.4-0.5Nm. 

Equipment is protected throughout by 

DOUBLE INSULATION

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 

Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-

TURKEY

Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:

18

      EI2041-EN-01-

180411

 

2

/5

ENDA

TM

 EI2041

 mA

  V

 ALR OUT

 EI2041

 mA

  V

 ALR OUT

Please see page 5 for Modbus Connection Diagram 