background image

 Independent alarm

 Deviation alarm

PARAMETER LIST

I.typ

 0-10              

             

Initial Value

CONFIGURATION PARAMETERS

Input type selection. (

0-20

mA,

 4-20

 0-1  0-10

)

mA,

V,

V

d5p.C

 Prc5              

Indicator configuration. (

prc5 : 

Process value, 

Pr.Un : 

4 Seconds process value, 2 Seconds 

Unit

 value.)

ratE

 5lo.1              

Hold

 nonE              

Indicator holding parameter. ( 

nonE 

: instant measurement value,  

lo. : 

minimum value,  

HI :

 maximum value is displayed.)

Unit

 nonE              

Measurement value. (Desired measurement value for unit selection).

Cal.t

 5.Inp              

Calibration type. ( 

5.Inp 

: Standard input type, 

U.Inp 

: User defined input type selection ).

d.Pnt

Decimal point selection. ( Adjustable between the 1th. and 3rd digits ).

L.5CL

Lower scale value. ( Adjustable between 

-1999

  and  

H.5CL

 value ).

H.5CL

  1              

Upper scale value. ( Adjustable between  

L.5CL

 and  

4000

 value ).

     OUTPUT CONTROL PARAMETERS

O.HY5

Output hysteresis value. ( Adjustable between 

1

  and  

200

 ).

O.5ta

Output status. (

Off

: Output not active, 

Lo:

 Becomes active below the setpoint output value, 

H1:

Becomes active above the setpoint output value).

     ALARM CONTROL PARAMETERS

a.HY5

Alarm hysteresis value. ( 

1

 and 

200

 ).

Adjustable between

a.5ta

Alarm condition. (

OFF:

Alarm not active. For independent or deviation alarm,  

H1: 

Alarm is active 

above the set value.  For band alarm, 

BI.HI

 : Activated in "in-band", 

Bo.HI

 : Activated in "out-band".) 

Lo:

 Alarm is active below the set value,  

a.typ

Alarm type. (

IndE : 

Independent alarm, 

dE

: Deviation alarm, 

band

: Band alarm)

     RS485 MODBUS COMMUNICATION PARAMETERS

adr5

Slave device address. ( Adjustable between 

1

  and  

247

 )

baUd

Baudrate. (Can be adjusted as ; 

Off

1200

2400

4800

9600

,

19200

 

kbps

 

)

 9600              

  0              

  0              

 2000              

  2              

  oFF              

  2              

indE              

  oFF              

O.5Et

Output set value. ( Adjustable between  

L.5CL

 and  

H.5CL

).

 2000              

a.5Et

 2000              

Alarm set value. ( 

L.5CL

 and  

H.5CL

).

Adjustable between  

O.Pon

Required relay-on delay time in order to set output to active state after power-up. ( Adjustable between 0 and 99 minutes ).

 01:00              

O.ton

Output relay-on delay time. ( Adjustable between 0 and 99 minutes ).

 01:00              

O.toF

Output relay-off delay time.  Adjustable between 0 and 99 minutes ).

 01:00              

A.Pon

Required relay-on delay time in order to set alarm output to active state after power-up. ( Adjustable between 0 and 99 minutes ).

 01:00              

A.ton

Alarm output relay-on delay time. ( Adjustable between 0 and 99 minutes ).

 01:00              

A.toF

 01:00              

Measurement ranges. 

Fa5t 

: Average of   1 measurement value is gathered in 200msec.

5lo.1 

: Average of   4 measurement value is gathered in 200msec.

5lo2 

: Average of   8 measurement value is gathered in 200msec.

5lo3 

: Average of 16 measurement value is gathered in 200msec.

             

Initial Value

             

Initial Value

             

Initial Value

Alarm output relay-off delay time.  Adjustable between 0 and 99 minutes ).

 

A.tyP.

=

indE

A.5Et

OFF

OFF

ON

ON

 A.5tA.

Hi

 

A.5tA.

Lo

OFF

ON

 O.5tA.

Hi

 

O.5tA.

Lo

O.5Et

OFF

ON

O.Hy5

O.5Et

O.Hy5

A.Hy5

A.5Et

O.5Et

:Output set value

A.Hy5

A.Hy5

A.5Et

:Alarm set value

 Band alarm
 

A.tyP.

bAnd

O.5Et

OFF

OFF

ON

ON

A.Hy5

A.Hy5

 A.5tA.

Bo.Hi.

 

A.5tA.

Bi.Hi.

O.5Et + A.5Et

O.5Et 

-

 A.5Et

O.5Et + A.5Et

O.5Et 

-

 A.5Et

A.Hy5

 A.tyP.

dE.

 A.5tA.

Hi

 

A.5tA.

Lo

O.5Et + A.5Et

OFF

OFF

ON

ON

A.Hy5

A.Hy5

O.5Et + A.5Et

O.5Et

ALARM CONDITIONS

OUTPUT CONDITION

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 

Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-

TURKEY

Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:

18

      EI2041-EN-01-

180411

 

4

/5

ENDA